The automatic switch operates without load: what are the reasons and what to do

The reasons why the automatic machine knocks out can be divided into three categories. The first reason is a defect in the machine itself, the second is something wrong with the load, and the third is problems in the controlled line. The solution to the problem of troubleshooting is to gradually localize sections of electrical wiring. The correct verification algorithm will significantly speed up and simplify the search.

Differential automatic

Quite often, a difavtomat is installed in the electrical panel of an apartment or private house.
The reasons why he kicks out are a little more complicated. The fact is that this device combines two protective devices: an RCD and a circuit breaker. Consequently, the reasons that lead to its operation are more extensive and relate to various factors. We discussed above what causes the circuit breaker to turn off. The same reasons influence the automatic device and cause it to operate. But, in addition, the differential device also works as an RCD, therefore, it responds to leakage current, which is somewhat more difficult to find.

Reasons for triggering

Let us analyze the main reasons for the operation of this protective device and possible places where leakage current is generated.

First of all, if the automatic circuit breaker has tripped, you need to inspect it and, if necessary, tighten the contacts

Also, when examining the protective device, pay attention to the wiring in the electrical panel. Perhaps the phase wire lies on a metal casing that is grounded

This will not cause a short circuit, but may cause the machine to kick out.

If everything is normal in the electrical panel, it means that there is a current leak in the circuit that the device protects. This can happen in several places:

  1. The cause can be any electrical appliance. If it penetrates the body, the difavtomat is guaranteed to turn off: this is one of its main functions, to protect a person from electric shock.
  2. Perhaps the consequence was the old electrical wiring, or rather, its worn insulation: current leakage gradually appears through microcracks, to which the difavtomat reacts. If the wiring is new, a leak may occur in a poor connection or if the wall is damp, for example due to flooding.
  3. A common mistake made by inexperienced electricians is shorting the neutral wire with protective grounding. This is strictly prohibited, since it leads to the operation of protective devices such as RCDs or differential devices.
  4. Damage to the case or sticking of the test button can also cause the device to trigger. In this case, it is necessary to replace the faulty device.
  5. Weather conditions, namely a strong thunderstorm, often lead to the automatic machine being knocked out. This occurs due to strong atmospheric discharges, which enhance natural current leakage. In this case, you should wait until the storm subsides and then turn on the voltage.
  6. Unprofessional installation or hastily installed wiring leads to the fact that the electrical connection diagram of the differential device is not followed. This leads to the fact that it periodically knocks out for no apparent reason.

The serviceability of the device must be checked periodically. To do this, when the load is removed, press the “test” button. A working difavtomat should turn off. If the device does not turn off, it does not perform protective functions, and it is better to replace it with a working device.

Methods for detecting a leak

To find the location of the leakage current, after the automatic circuit breaker has tripped, you need to unplug all electrical appliances from the outlets. After this, the protective device is turned on. If the shutdown does not occur again, it means that some device is breaking through to the housing. You can detect it by calling it with a multimeter.

If the differential device continues to knock out, then the problem is in the wiring. It is best to start an inspection of the electrical circuit with socket groups and distribution boxes

Particular attention should be paid to the places of connections and twisting of wires, the integrity of the insulation and the reliability of contacts

After checking all contact groups in the electrical network, proceed to the next stage. It is necessary to check each individual line for current leakage. It is recommended to start from the electrical panel, gradually moving deeper into the house or apartment. Having determined the line or junction box after which the differential current occurs, all twists are disconnected and each wire is tapped.

Thus, there is a circuit where the insulation is damaged. If necessary, change the wiring or isolate the damaged area. Sometimes you have to remove the wire from the wall to do this if the wiring is hidden. But such cases are quite rare: if the electrical wiring is very old, it is better to replace it during repairs or when installing a differential device.

The circuit breaker of the socket group is triggered

First, unplug all electrical appliances from the outlets. And try turning on the machine. Knocked out again? Open all electrical boxes and sockets. 90% of all damage occurs at the contact junctions. If a visual inspection shows nothing, then you will have to disconnect the wires in the boxes. After this, take a multimeter, and in diode testing mode, connect one probe to the phase conductor and the other to the neutral conductor. If there is a short circuit, the device will emit a signal and show zero resistance.


This way you can find a piece of damaged wiring from one junction box to another or to an outlet. In order to turn on the machine, this section will have to be disconnected and subsequently replaced.

The machine in the dashboard constantly knocks out

Quite often, owners of private country houses and apartments wonder why the machine in the control panel is knocked out without a load, in the absence of visible reasons. In addition to the factors already discussed, a similar situation often arises due to overloads in the electrical outlet network.

When drawing up a project and installing electrical wiring, it is impossible to determine with absolute accuracy the degree of load on each group of sockets. Usually there is a separate circuit breaker for 3-4 sockets. However, if there is a powerful protective device, the rated current of the connected sockets can be significantly lower.

In such a situation, an overload will certainly occur, especially if an iron, stove, microwave and other powerful equipment are simultaneously connected to the same group of outlets. As a result, the circuit breaker inevitably trips. It is possible to eliminate such cases by evenly distributing the powerful load between several outlet groups. If this is not possible, you should not connect several high-power consumers to the electrical network at once.

Sometimes it happens that the machine is knocked out and does not turn back on. Here the reason may be the thermal release, which gets very hot. To turn the device back on, just let it cool down and it will work normally again. The machine is often triggered by a faulty device that consumes increased current. As a result, the network is overloaded and the circuit breaker is knocked out. The solution to the problem, as already noted, is to turn on the devices one by one until the faulty one is discovered among them.

It happens that the machine itself is not connected correctly. Cores that are loosely tightened in the terminals lead to heating of this place and the operation of the thermal release. The reason is visible to the naked eye when not only the wire insulation becomes burnt, but also the body of the device.

This is interesting: Choosing a circuit breaker - consider the question

Overload


If the automatic circuit breaker does not turn off immediately when the load is turned on, but after a few seconds or minutes, then there are clearly overload currents present, but their values ​​are not sufficient for instantaneous operation. Therefore, the shutdown occurs due to the operation of the thermal release. There are too many consumers on the line. This happens when several powerful devices are connected to one socket through a tee. It is necessary to remove part of the load, switch electrical equipment to other lines, if possible.

If the wiring cross-section allows, you can add the number of sockets and replace the difavtomat with a device with a higher rated current.

By the way, if the automatic device is triggered by a thermal release, it does not turn on immediately. It needs time for the bimetallic strip to cool. This is also a good sign for localizing and troubleshooting.

How to extend the life of a circuit breaker

Remember two tips:

  • Do not overload the protected line with a current higher than the rated current.
  • Do not turn off the machine under load.

If everything is clear with the first tip, then the second one is a little more complicated. When current flows through the contacts and you are about to separate them, an arc occurs. This happens due to the truth of the laws of commutation: “The current in the inductance cannot stop instantly.”

Even if the load is active, for example a heater, the cables have their own parasitic inductance. It is even more dangerous to open a circuit breaker if a load such as electric motors or lighting networks with a large number of chokes (DRL, DNAT, LL) is connected to it - the inductance is even greater, and so is the arc. Hence contact defects, their charring, accelerated wear and sticking.

We have become familiar with what defect is caused by what. Circuit breakers last quite a long time if they operate within rated conditions. Modern machines cannot be repaired, so we do not recommend disassembling them; it is better to replace them with a high-quality analogue, for example Moeller or ABB. For household appliances and active loads, use machines with the letter B; to connect a load with significant starting currents (motor), devices with the letter D are better suited, and the number after the letter indicates the amount of permissible current. Avoid connecting oxidized wires and always tighten terminals. By adhering to these tips, circuit breaker malfunctions will occur much less frequently, and you will not have to worry about the safety of the wiring in your apartment or house.

Finally, we recommend watching a useful video on the topic:

You probably don't know:

  • Socket malfunctions and ways to eliminate them
  • How to find a short circuit in wiring
  • Reasons for triggering the automatic device
  • How to check the performance of an RCD

Published: 01/27/2018 Updated: 01/31/2018

Reasons for shutdown in a working electrical network

The reasons for knocking out automatic devices in a working network are the same as in newly introduced electrical wiring. When analyzing the situation, it is necessary to take into account the general condition of the electrical network:

  • what wires were used;
  • type of insulation;
  • two-wire or three-wire wiring.

You need to find out if there is local grounding. On the latest models of automatic machines, an indication platform has appeared on the front panel. It helps to determine the reason for the triggering of the automatic device.

If, when knocking out the device, the pad did not go beyond the plane of the front panel, then this means leakage currents; if it did, then the operation of the device caused a short circuit or overload.

It may be the other way around, you need to look at the instructions for this device. This feature, of course, makes troubleshooting easier.

What not to do if the machine turns off

If the plugs are out, you shouldn’t try to get into the dashboard yourself, you need to figure out the reason

You should not climb into the electrical panel yourself if the plugs in the apartment are knocked out. It is necessary to understand the reasons. If there is no light in the entire entrance or in neighboring houses, most likely there is a problem at the substation. All household appliances must be unplugged from their outlets so that they do not burn out when power is restored in the event of a power surge.

When the problem affects only one apartment, you need to open the flap and see which of the plugs has worked. The white button will protrude a few mm from the housing. When you press it, the fuse turns on.

Modern circuit breakers are installed on new construction sites. If the pedals of the device are lowered, it means that the plugs are knocked out. To restore electricity in the apartment, just move the lever to the upper position.

Sometimes people consider constant power outages to be the norm and do not think about the wear and tear on the circuit breaker. Sooner or later the button gets stuck and the device stops functioning in the correct mode. Due to excess voltage, an emergency situation occurs, which in most cases leads to a fire.

Briefly about circuit breakers

Automatic machines must be checked for functionality in order to avoid an emergency.

Circuit breakers or circuit breakers are electrical mechanisms whose main task, in the event of abnormal or emergency situations, is to de-energize the problem line or the entire room. It monitors the voltage in an electrical circuit in real time.

Automatic switches are widely used due to their reasonable price, reliability and ease of use, installation and maintenance. A large number of modifications allow the device to be installed in electrical installations of high and low power. Switches are also available with manual and remote control.

Troubleshooting

If the differential circuit breaker has tripped, you can try to turn it on again. This will eliminate the possibility of triggering during a power surge. If the attempt is unsuccessful, then you need to disconnect the consumer from the outlet controlled by the automatic device and try to turn it on again. Did you manage to turn it on? This means the problem is consumer isolation.

In the case when the attempt is unsuccessful and the device works as before, you need to look for the reason further. Now you can unscrew the outgoing wires L and N from the device and thus check its functionality, without load. A working device should turn on and operate when you press the “TEST” button.

The algorithm for searching for the reason for the operation of the differential machine is shown in the diagram:

We also recommend watching a video that clearly demonstrates common errors when connecting differential protection, which results in the device being knocked out:

So we looked at the main reasons why the automatic switch in the dashboard works. We hope you now know what to do to solve the problem!

Be sure to read:

  • Errors when installing electrical wiring
  • Why does a circuit breaker trip?
  • Reasons for tripping the RCD in the panel
  • How to connect a difavtomat

How to check a difavtomat at home? — Handyman's Handbook

Currently, effective and quite convenient devices have appeared on the market of electronic switching devices - differential automatic machines.

They are compact and contain several protections at once: maximum current (from short circuit), thermal (from exceeding the rated load for longer than the specified time) and RCD (protecting people from electric shock when the insulation of wiring or electrical appliances deteriorates).

With the advent of these devices, there is also a need to check their serviceability. In this article we will tell you in detail how to check the operation of a difavtomat using all available methods.

How to check a differential circuit breaker and RCD

Unfortunately, testing such important characteristics as response time, overload characteristics, and short-circuit current with automatic devices at home will not work. Since to check these parameters it is necessary to have special instruments and equipment.

The difference between a difavtomat and an RCD

For the home, it is quite enough to check the differential circuit breaker for operation and compliance with the leakage current protection, at which the circuit breaker turns off and provides protection against electric shock.

A differential circuit breaker differs from an RCD device only in the presence of a circuit breaker. That is, this is the same RCD plus an automatic device in one housing.

Therefore, all checks for the suitability of a difavtomat are similar to testing an RCD.

Types of automatic machine checks

There are several ways to check the functionality of protective devices, these are:

  1. Check with the “TEST” button located on the device body.
  2. A regular battery from 1.5 V to 9 V.
  3. A resistor that simulates a violation of the insulation resistance of electrical wiring and household appliances.
  4. A simple permanent magnet.
  5. A special electronic device for checking the parameters of differential circuit breakers and RCDs used in industry.

Before purchasing a security device, you need to know what tasks it will perform. For fire-fighting purposes, the difavtomat and RCD are selected with a leakage current of 300 mA. If protection against electric shock is required, a device with a leakage current of 30 mA is used. In damp and damp bathrooms or baths, protection with a leakage current of 10 mA is required.

Troubleshooting network problems

Having previously found out why the RCD is triggered, it becomes easier to specify the problem. So, if the problem is poor-quality installation, then you should disassemble the entire line and reconnect all phases, guided by a special diagram. In cases where the RCD has tripped and does not turn back on even when the circuit breakers are lowered, the protective equipment will have to be completely replaced.

The search for the “culprit” can be done in two ways:

Visually inspect each device, try to identify signs of malfunction (inoperability, charred wires, damage to the case, cord or plug, unpleasant odour).

Connect each unit to the network one by one, observing the reaction of the RCD, which will trip again when the faulty device is connected.

The reason why the RCD trips without load is faulty wiring. This outcome is the most time-consuming and energy-consuming to eliminate a possible problem. Before completely replacing the line with a new one, try the following:

  • Carry out a thorough inspection of all sockets, switches, distribution boxes and panels for the “zero” to come off, the core to be exposed and moisture to enter.
  • Check to see if the overhead light is the culprit.

An RCD is a guarantee of our safety, therefore, when it is triggered, it is necessary to inspect all electrical wiring, and if a problem is identified, immediately eliminate it to avoid recurrence.

Next steps

It is important to understand that the RCD is connected rigidly according to the diagram and any deviations from it can cause it to trip. The troubleshooting process begins with determining the reasons why the RCD worked, identifying the reasons for this behavior of the device

Maybe:

  • Is the RCD itself faulty?
  • It's a matter of equipment failure
  • There was an insulation breakdown somewhere,
  • Sockets and light switches were installed incorrectly.

In other words, you need to look for a loophole where the current leaks and eliminate it. To do this, you will need an appropriate device that allows you to “ring the circuit” and look for specific breakdowns - a tester or multi-ohmmeter.

Why does the protection work?

There are only three reasons why a traffic jam can be knocked out:

  • Short circuit;
  • Excessive load;
  • Damage to the device itself.

The most dangerous reason is a short circuit, which can be triggered by a weakened or melted insulating sheath of wires, water getting into them, or a burnt electrical appliance.

With such an outcome, a sharp jump in current occurs in the network, the wiring heats up, and the voltage quickly drops, and traffic jams detect the emergency and automatically de-energize the network. Otherwise, a fire or wiring will burn out.

If plugs in the meter often break out without dire consequences, then the reason lies in the network overvoltage. By connecting several devices to one branch at once, you risk exceeding the permissible rating, which for a machine is 16 amperes, and for one plug is no more than 2.5 kW.

It is not often that a knocked-out plug signals a malfunction, because, like any device, it can simply fail and turn off falsely. Also, a sudden breakdown of a large household appliance triggers the protection mechanism.

Testing with a AA battery

A very simple method is to check the RCD using a AA battery. It allows you to check the functionality already during the purchase of the device.

To directly carry out testing, a piece of wire with a length of at least 10 centimeters is connected to any pole of the device. The second wire is connected at the bottom of the device during manufacture. After this, the AA battery is brought to both wires.

When the wires touch plus and minus, the RCD should trip. If this does not happen, you need to reverse the battery poles and repeat the test. If the device is working properly, the shutdown lever should be knocked out.

The main thing is prevention

In conclusion, let's look at how the electrical wiring in the apartment should be arranged so that machines and traffic jams are knocked out as rarely as possible. The main thing here is to turn on the protective automatics for the sake of pennies of savings only in the break of the phase wire, as on the right in Fig. - a grave mistake.

Correct and incorrect inclusion of protective automation in apartment electrical wiring

Firstly, in some emergency situations on a network with a solidly grounded neutral, phase voltage may appear on the neutral wire; what this entails – see above. Secondly, such inclusion does not guarantee against problems with electricians: if the wiring neutral is solid, then there are ways to steal electricity. Let someone else do this, but the dispatcher will notice, and it will be up to you to prove to the inspector that the camel is not you.

Any automatic protective equipment must break all suitable conductors when triggered (in networks with a solidly grounded neutral - 2, phase and zero), this is the first thing. And secondly, all potentially emergency devices and devices must be turned on each through their own current protection circuit breaker, on the left in Fig. If you live in an apartment building, for which it is not possible to install a protective grounding circuit, these rules must be strictly followed.

Display all materials with the tag:

Go to section:

Specifications

The main technical characteristic of a differential circuit breaker is the rated current. This indicator is standardized and corresponds to 6A, 10A, 16A, 25A, 50A. When applying this marking to a protective device, this value is indicated together with the performance indicator, which are expressed by the symbols: B, C, D.

The next characteristic is the voltage cut-off current. For almost all models these parameters correspond to: 10mA, 30mA, 100mA, 300mA, 500mA.

The characteristics of the device indicate the rated voltage. It can be 220V in a single-phase network and 380V in three-phase power lines.

The magnitude of the leakage current and selectivity are characteristics of this device. In accordance with this indicator, devices may have the following designations: A - devices that are triggered by leakage of current of an alternating parameter; AC - devices that are triggered by current leakage of a constant value; B – devices that are switched off when the two above-mentioned circumstances occur.

The following indicates the type of built-in RCD. On the surface of the device, this parameter is indicated in letters or in the form of a picture.

Since the difavtomat is based on a built-in RCD, the principle of selectivity also exists in this device. This principle lies in the time period of the response delay. That is, the protective device that is closest to the electric meter should have the longest shutdown delay time.

In accordance with this, devices are marked with the letter S, which indicates a shutdown delay of 200-300ms, or with the letter G - 60-80ms.

Reasons why a circuit breaker trips

There may be several such factors; we will look at each of them in detail.

Permissible load exceeded

Each machine has its own characteristics, which are reflected on its body. One of these indicators is the rated current that the device can carry. If this current is exceeded, after a while the machine is knocked out: this is an automatic thermal release that has tripped to protect the electrical wiring.

There are two ways to solve this problem:

  1. The easiest way (and the most recommended by electricians) is to alternately connect electrical appliances to the network to avoid overloads. For example, if you have a 16A machine installed, it can “withstand” a load of 3.5 kW;
  2. You can replace the circuit breaker with a more powerful one, for example, install the device at 25A. The machine no longer knocks out, since it is designed for a load of 5.5 kW. But this method of solving the problem is used only if the old wiring has been replaced with a stronger cross-section (minimum 2.5 square meters for copper conductors).

Note! If an overload shutdown occurs, it will be possible to restart the machine only after some time, when the thermal release has cooled down

A short circuit has occurred

Another common reason why a machine breaks down is a short circuit. A short circuit can occur due to several factors and in different places. Let's look at this issue in detail.

Short circuits in electrical appliances are very easy to detect. Usually, if there is a short circuit in any electrical appliance, it stops working. Also an indicator is a blackened case or melted wires. In this case, it is enough to disconnect the device from the network and turn on the machine, it will not knock out.

If there are no obvious signs of a short circuit, you should turn off all electrical appliances. After turning on the voltage, turn on the consumers one by one. When a closed device is plugged into the network, the machine will trip again or it will be discovered that the consumer is faulty.

If everything is fine, try turning on the lights in each room. It happens that the socket or light bulb shorts out, so it knocks out the protection.

Short circuit in electrical wiring

If the above steps did not detect a short circuit, it may be in the wiring. Finding the location of a short circuit in the wiring, especially if it is hidden, will be much more difficult. To do this, you need to ring each line with a multimeter. But first, you can check the distribution boxes and sockets. It is in these places that short circuits most often occur.

When checking distribution boxes and sockets, you should first of all pay attention to melted wiring, exposed ends or loose contacts. Such shortcomings need to be eliminated: the ends are securely insulated, and all contacts are tightened

The circuit breaker has failed

You shouldn’t rule out the situation when the machine itself is out of order, this also happens. The reason for this may be a manufacturing defect in the design or mechanical damage to the housing. There are times when you just need to tighten the contacts on the device itself, which have become loose over time. If this does not help, replace the machine with a similar rated current. This is quite easy to do and won't take much time. If the shutdowns stop, it means that the cause was found and eliminated.

These are, perhaps, all the factors that lead to the circuit breaker tripping. There are not very many of them, but any one can cause a shutdown. Let us remind you that if the protection has been triggered, in order to avoid more serious consequences, you should not postpone the inspection of the electrical network until later.

Other reasons

The reason for knocking out the automatic rifle can be anything. This includes increased humidity, which penetrates into the junctions of wires in sockets, junction boxes, and accidental damage to the insulation of wires hidden under the casing by screws or nails. There may be a manufacturing defect that does not appear until several years later.

Finding such faults is quite a troublesome task and takes a lot of time, even in the case of open wiring. The easiest way is to find a break in the line and eliminate the fault by simply replacing the wire.

If necessary, replace the outlet with a waterproof one. Sometimes you come across low-quality wires with insulation that does not meet the declared characteristics. This also does not appear immediately. You'll have to change the wiring. If they laid it in corrugations, then you were lucky. You will do without dusty work.

Checking the circuit breaker

Do a basic check of the circuit breaker.

  • Turn off the power supply to the apartment panel;
  • Turn off all circuit breakers;
  • Click the circuit breaker charging lever. It should turn on and off with a characteristic “click” sound.
  • If a click is not heard, the machine is faulty and requires replacement.
  • If there is a click, use a measuring device to measure the resistance between the terminals of the circuit breaker. When "on" machine resistance should be close to zero. When "off" The resistance of the machine should be close to infinity.

Generally speaking, factory failure of circuit breakers is not that uncommon and the choice of circuit breaker is important. What can we say about the malfunctions of machines that arise during operation?

A malfunction of the circuit breaker itself cannot be ruled out as the main reason for its periodic shutdown.

Installing a circuit breaker is a simple matter, and such a replacement can save you from major work to find other electrical faults in the apartment.

Ehto.ru

Complexity of connection diagrams

Connecting any equipment requires some time. The more time you spend on one operation, the less work you will do. It is for this reason that all kinds of press tongs, strippers and other tools were invented - to reduce the time spent. This point implies the complexity and speed of connecting RCBOs compared to the “Uzo + automatic” combination.

The connection diagram of the RCD and the machine is assembled as follows: the phase wire is first connected to the circuit breaker, then it leaves the machine and is connected to the upper “phase” terminal of the RCD. The neutral wire is connected directly to the upper “zero” terminal of the RCD. Then the phase and zero move from the lower terminals of the RCD to the consumer.

The connection diagram for the differential machine looks a little simpler: here the phase and neutral wires are connected directly to the upper terminals of the differential (each to its own terminal). From the lower terminals the power goes to the consumer.

This results in much less switching and additional connections. Consequently, when operating difavtomats, the internal installation of shields is significantly simplified.

What to do?

First of all, determine which circuit breaker tripped in the electrical panel. If this is only a general circuit breaker, then a short circuit has occurred directly in the electrical panel. Upon careful inspection, this will be noticeable, and you will also smell the smell of burnt plastic. If you have the skills, you can begin to repair the damage, otherwise you need to call a specialist.

When any linear circuit breaker (line of sockets or lighting) is triggered, you need to look for a fault specifically on the disconnected line.

Line of sockets. We remove all plugs of electrical appliances from the sockets and try to turn on the machine. If the machine does not turn off, then the problem is a breakdown of one of the devices - electricity consumers. Finding it is not difficult - plug the devices into the sockets one by one and the circuit breaker will “knock out” when the faulty device is connected. If it “knocks out” when all electrical receivers are turned off, the problem is due to damage to the electrical wiring. Then you need to look for a fault in sockets and distribution boxes - tighten the internal contacts first. If this does not lead to anything, then we disconnect the wires in the boxes and “call” them with a multimeter for the fact of a short circuit. This way you can understand which wire or cable needs to be replaced.

Lighting line. A similar principle of action in this case is to de-energize all lighting equipment on the line. If the machine turns on, then the fault is in one of the lamps. We turn on each of the lamps one by one, thus finding the faulty one. If we find it, we inspect the contacts in the electrical socket and begin to repair it. If the machine does not turn on even when the lamps are turned off, then the electrical wiring must be repaired (the problem must be looked for in the same way as in the case of a line of sockets).

Knocking out when putting electrical wiring into operation

In the case of new construction or major renovation of a home, new electrical wiring is laid and, accordingly, an electrical panel is installed with protection devices against leakage currents and short circuits.

After installing and turning on the machines, a malfunction appears. The difavtomat knocks out either immediately or after connecting the load.

In this case, a defect in the device itself is excluded, since it was checked upon purchase. The only thing you need to do is check the values ​​of the breaking and rated current of the difavtomat.

They must correspond to the values ​​previously calculated and indicated in the diagram. The second reason can be eliminated by replacing the load with a regular table lamp.

This is usually done on an already operating power supply system. When you turn on the electrical wiring for the first time, you need to start by checking the installation.

Checking the differential machine begins by turning on the device in test mode. If it works, it means it's working. The sequence of further actions is as follows:

  • make sure the load is off;
  • turn on the machine, if it is knocked out, it means that the conductors are connected incorrectly;
  • make sure that the neutral wire is connected to the upper contacts marked N, and the phase wire is connected to contact L;
  • check the lower contacts of the difavtomat for correct connection of the wires from the controlled line;
  • try turning on the security device.

Pay attention to where the neutral wire comes from. It should go to the upper contact from the zero bus.

The neutral wire from the controlled line, coming from the distribution box, is connected to the bottom terminal. If it’s knocked out again, then you should check the connections in it itself.

AV is out of order: what to do if the plugs are knocked out

Another reason for the machine to operate is a short circuit in the electrical wiring. If the fuse has tripped due to a short circuit, you need to look for the cause. There is an effect on the phase, which in some place touches the zero, because of this a short circuit occurs and the AB protects and is instantly triggered. If electrical appliances are unplugged from the sockets and the plugs are knocked out, it is necessary to completely check the electrical wiring. This takes quite a long period of time and, in addition, you need to have the skills to find a fault, or maybe two at once. The first thing you need to do is examine all sockets and switches and check the quality of the TPG connections to the terminals. If the electrical wires are loose, the screws should be tightened.

After the sockets, you need to study the distributors. Understand that the connection of the electrical wires in them is normal, there are no bare spots that could short out. After the boxes, you need to check the lighting devices. Very often, inexperienced electricians forget to check the chandelier after the AV trips without a load. After this the light bulb burns out. It is necessary to check the reliability of the connections, as in the situation with sockets. Finally, you need to check the electrical wiring, which is usually hidden in the wall. In this case, it is correct to use a special device that will help quickly detect a short circuit. But hardly anyone at home will have it on hand, so a multimeter will help get out of the situation. Here are the reasons that turn off an electric machine and how to eliminate them.

The most rare reason, which can be the same, is a low-quality MTA machine, which kicks out due to a manufacturing defect.

You should check the machine if you are 100% sure that:

  • Electrical appliances are in good working order;
  • Electrical wiring is OK;
  • There is no talk of overloads.

Replacing the machine with a similar one will help correct the situation; you can also replace the electric meter. This will definitely solve the problem. To avoid such a situation in the future, electricians are advised to get acquainted with the rating of the best brands of circuit breakers and select one circuit breaker and a meter from the list. It’s also a good idea to read consumer reviews. In addition to the listed reasons why the AV switched off in the electrical panel, there are also other, rare situations.

Methodology for testing difavtomats

Each specific test method for protective disconnecting devices is developed taking into account the specific characteristics of the site in which they are operated.

In any case, it should be based on the algorithms discussed in the above standards. In the package of documents submitted for certification of the electrical measuring laboratory, it must be issued with a separate instruction.

It should be noted that tests of this type are carried out with the supply of powerful current pulses, which often leads to unscheduled operation of the RCD, therefore the practical technology for testing a difavtomat should include the assembly of special measuring circuits or switching separation of the machine and the RCD.

Considering the wide variety of hardware solutions for the differential module and, as a consequence, the unpredictability of their behavior, they most often resort to the second option, opening the circuits connecting the RCD and the AV.

Wires connecting the RCD and the machine

Measurement of time-current parameters is carried out using special equipment that allows monitoring the time parameters of powerful current pulses. Electrical laboratories providing this type of service usually use the UPTR device for these purposes.

UPTR device in operation

Tests and measurements are carried out using the diagram shown in the following figure:

UPTR circuit

The measurement results are recorded in a work log and, after mathematical processing, are drawn up in the form of a test report.

The electrical engineering laboratory "Mega.ru" accepts orders for testing all types of electrical installations, including residual current systems. You can clarify the details of cooperation and place an order for work by calling the numbers posted in the “Contacts” section.

Briefly about circuit breakers

Automatic switches are designed to act as switching devices necessary to conduct load current during normal operation of the equipment and open the electrical circuit in emergency mode at high or low voltage.

AVs are widely used due to their ease of installation, reliability in operation, safety during replacement and maintenance, speed of response in case of short circuit currents or abnormal conditions. Such machines are installed in electrical installations with both low and high power.

There are devices with manual and remote control. In abnormal conditions, the switch operates automatically. All devices are equipped with an overcurrent release. Some models are equipped, in addition to the maximum and minimum current release. Such circuit breakers are designed to replace switches or fuses in plug fuses, which provides more reliable protection for household appliances and connected equipment.

ABs are produced mainly for amperages from 6.3A to 6300A for alternating current installations up to 1 kV, with a different number of poles. These can be one-, two-, three- and four-pole circuit breakers.

You can find out more about the design of a circuit breaker in our corresponding article. Now I would like to additionally tell you that protection against abnormal conditions is provided by an electromagnetic release, thanks to which the device is turned off.

There are two types of releases:

  • electromagnetic or maximum release against short-circuit and overload currents (without time delay);
  • thermal (electronic), triggered at currents significantly exceeding the rated values ​​of load currents (with a time delay).

Both types of protection must comply with the manufacturer's regulatory documents (PTEEP in Appendix 3). In order for the device to work properly, it must be checked before installing the circuit breaker. This operation is called loading the machine, which we will now discuss in more detail.

Checking the RCD using a control lamp

Anyone who cares about their safety should carry out a control check of the correct operation of the RCD at least once every few months. You can check the operation of the RCD yourself using a practical and reliable method. The device works in such a way that when a current leak occurs, it is triggered.

To check the device in this way, you will need an electric wire, an electric incandescent lamp, a socket, resistances and special electrical tools. Before creating a leakage, it is necessary to calculate how much leakage current can be created. It depends on the current that flows through the electric lamp.

How to check the operation of an RCD using a lamp:

  • Connect two resistors in parallel. For their power to be 10 W, the resistance must be 2.35 kOhm.
  • Using wires, these connections are connected to an electric lamp.
  • If there is a protective zero connection to the sockets in the room, then you can check the operation of the RCD using any socket.
  • One wire must be connected to the phase, the other wire must touch the protective zero.

As soon as the action is completed, the device should work instantly. If there is no protective zero in the sockets, then checking each socket will not be possible. If this is the case, you can check whether the RCD is working through the electrical panel.

Rating
( 2 ratings, average 5 out of 5 )
Did you like the article? Share with friends:
For any suggestions regarding the site: [email protected]
Для любых предложений по сайту: [email protected]