Let's find out how to connect a gas generator to the network at home


Using a changeover switch

In fact, this is also a connection to a distribution machine, only without the need to disconnect the input wiring.
A three-position switch is mounted in front of the machine to avoid unscrewing the wiring. The task of this switch is to switch the network power from one branch to another (from an external network or generator). To perform this function, you need to select a switch with 4 input terminals (2 “phases” and 2 “zeros”), since the generator has its own “zero”, and a three-terminal switch will not work in this case. An alternative to a 3-position switch would be to install a pair of two-way machines next to each other, but rotated 180 degrees to each other. The keys of both devices are secured with pins through holes specially provided for this purpose. In operation, when switching the keys, for example, down, such a combination of machines will block the power supply to the network from the external line and open the way for the electric current generated by the autonomous generator. The opposite action with the keys will lead to the passage of current from the power line and blocking the flow of energy from the generator.

For convenience, such a switch should be installed in close proximity to the generating device, since it is launched in a certain sequence:

  1. Direct start of the generator engine.
  2. Warming up the device.
  3. And only then connect the load.

Naturally, it is more convenient to perform these actions and control the process in one place.

To prevent the generator from running in vain, that is, when voltage is already supplied to the backup line, it is necessary to mount a terminal for the lamp in front of the switch. Turning it on will signal the need to turn off the autonomous source and switch to supplying electricity from the main power line.

How to properly connect a generator to the home network

Connecting a power plant to your home network is possible in several ways. A popular option is to connect the network reserve through a changeover switch or packet switch.


How to connect a generator to the network at home

For the case of automatic connection of a power plant with auto-start, an ATS system (automatic transfer of reserve) is used. It is also possible to connect various household appliances through an extension cord with several sockets. In this case, the extension cable cross-section is calculated based on the total load current.

Installation of a changeover switch

The easiest way to connect an electric generator to your home is to install a changeover switch or packet switch. The batch switch is installed on a DIN rail in the electrical panel of the house. The switch is placed near the electrical panel.

The external electrical network is connected to the upper contacts of the switch, and the lower contacts are used to connect the cable from the power plant. The middle pins connect the home network input. After installing and connecting the changeover switch, put on the protective housing.


Connecting the generator through a switch and automatic transfer switch (ATS)

It is recommended to connect the switch after the electric meter and before the water dispenser. When the mains voltage disappears, the generator is started. After the engine has warmed up, the changeover switch is moved to the lower position (to the contacts going to the generator). After the network appears, the switch is moved to the upper position and the power plant is turned off.

Connecting the power plant via ATS

For automatic control of the power grid and automatic transition to a backup generator in the event of a network failure, there is an ATS device with automatic start-up of power plants. The AVR system monitors the electrical network and, when it disappears, disconnects the magnetic starter from the network and turns on the autostart of the generator.

When the generator reaches its rated speed, another magnetic starter is turned on, which connects the home network to the power plant. When the network is restored, the ATS disconnects the home network from the generator and connects another starter to the external network.


Connecting a 3-phase generator to a three-phase network at home

This transition from the backup generator does not occur immediately after the network appears, but with some time delay until the external network becomes stable. For the case of three-phase networks, it is recommended to install a single-phase generator, and connect all necessary household appliances and equipment to it via a separate backup electrical wiring with a changeover switch.

In a private home, AVR does not always pay off, since it always has to be controlled. With the same success, you can use a changeover switch and start the power plant manually. It is recommended to use a switch in case of rare outages of the external network.

Power plant grounding

For electrical safety purposes, in cases of voltage breakdown on the generator housing, a grounding connection is required. For power plants, you can make a simple ground loop. A piece of steel pipe, a pin or a metal rod with a diameter of 20 mm and 1.5 meters in length, is driven completely into the ground.

Generator grounding

At the end of the grounding conductor it is necessary to weld a bolt for the grounding conductor. As a conductor, a copper stranded flexible wire of 4-6 mm², with external insulation, is used.

The installation location of power plants must be selected taking into account fire safety, noise, precipitation and room temperature.

A simple way to organize auto switching

In order not to manually switch the switch every time there is no electricity supply from the main power supply line of the household, you can make a fairly simple circuit that allows you to automatically switch from an external network to an autonomous one after starting the gas generator.

To install an auto-switching circuit, you will need two starting devices (contactors) that have a cross connection. During their operation, power as well as normally closed contacts will be involved. In addition to this set, if you need to provide the generator with a certain period of time for warming up, it is worth purchasing a time relay.

When voltage is created in the home electrical network from an external line, the main input contactor coil will keep the power contacts in the closed state, and the normally closed ones, on the contrary, in the open state.

When the voltage in the power transmission line disappears, the power contacts will open, and the normally closed ones will, accordingly, go into the closed state, which will allow, after a period of time specified by the temporary relay, after the generator is started, to supply voltage to the coil of the backup input contactor. As a result, the power contacts on the backup starter will close, and electric current from the gas generator will flow into the home network.

You may be interested in this Surge protector for household appliances and computers

When the centralized supply of voltage to the network of a private house is restored, the coil of the main starter will work, which will lead to the closure of the power contacts of this contactor and the automatic shutdown of power from the gas generator. The owner of the house just has to remember to stop the engine of the device for autonomous generation of electricity.

Through an automatic (distribution) switch

The ideal option is if the panel has an outlet. This method should not be confused with the one described above. On the electrical goods market, some ready-made panels are initially equipped with such outputs (it is recommended to choose them for private households). Sometimes, when assembling the panel yourself, they install an incoming AV, a meter, an RCD and one or two sockets for insurance, so it is convenient to carry out repairs. Then the generator can be connected there without any problems.

You need to be reliably aware that this is not an ordinary power outlet.

The rules must be followed:

  • the socket must pass at least 16 A or more under the power of the backup device;
  • AV at the input must be disabled.

If the described elements are not in the shield, then remove the input wires from the switchboard and connect the device directly to it. If RCDs and RCBOs are further installed, the polarity must be observed. Let us remind you: if you connect to the “firefighter” AB in front of the metering device, the circuit will work, but the meter will count its own electricity already produced. The introductory AB is sealed by energy sales, so more often than not the possibility of this option is completely absent. It is necessary to choose exactly the distribution (group, common) AB or RCBO after the metering device.

Algorithm of actions:

  1. Turn off the input machine. After connecting the backup source, it can be activated again, and this will be necessary before installing the control lamp.
  2. Unscrew the clamps on the switchgear terminals and remove the wiring.
  3. In place of the indicated cores, observing the polarity, especially if further than the RCD, RCBO, connect the cores from the generator cable.
  4. You can mount a light bulb on the folded wires, which will indicate the resumption of the main power supply; after installing it, the introductory circuit breaker is turned on.

Switch Connection

The simplest way to connect a generator is using a switch. The switch operates in three positions. In the initial position, the object is connected to a centralized power grid, without the participation of a gas generator.


When the switch moves to the next position, the object is completely de-energized. The next time you turn the switch, the power to the home network switches to a backup source - a gas generator.

Keep in mind that if the total power of all consumers is 6 kilowatts, then the switch must support at least 30 Amps.

Choice

The buyer must determine from the very beginning which technical parameters are the most important for him. It is worth taking a closer look at these indicators:

  • Weight.
  • Dimensions.
  • Power.
  • Fuel consumption.
  • Noise level.
  • Duration of work.

Automation and price are parameters that are also being looked at

This is important for those who are interested in how to connect a generator to the home network, the diagram of which is posted on specialized websites


Generator operation

By parameters

Many people first look for an answer to the question of how many phases a generator should have for maximum convenient operation. To do this, you need to understand what electrical appliances will be connected. Three-phase options allow connection to both single- and three-phase devices. Single-phase ones are combined with only one type of consumer. But this does not mean that models with more phases will be better under all circumstances.

At each phase, the maximum load should be no more than 30%. This means that in reality the owners will not be able to use more than a third of the rated power that the outlet initially has. For example, the rated power of a three-phase generator is 6 kW. This means that no more than 2 kW can be removed from a regular 220 V outlet. The load still needs to be distributed over several phases when connecting a single-phase generator to a three-phase network at home.

Note! For power, they also check the parameters of the devices that are planned to be connected

It is important to have a reserve of at least 20-30%. Otherwise, you may encounter problems such as overload and work stoppage. Too much fuel will also be consumed

Too much fuel will also be consumed

Otherwise, you may encounter problems such as overload and work stoppage. Too much fuel will also be consumed.

Type

Synchronous and asynchronous types of devices are available. The choice involves a careful study of the characteristics of each of the existing models.

Asynchronous

Their main problem is their inability to handle so-called peak loads. Although these devices can also be used to maintain normal voltage readings. They are suitable for joint use with equipment sensitive to voltage surges:

  • Electronic devices.
  • Computer Engineering.
  • Medical devices supporting gasoline generators.

Residual magnetization of the rotor is the main source of energy for such devices. Therefore, the service life of asynchronous generators is longer than that of their closest analogues. They do not require the use of cooling systems; the unit housing is completely closed. Thanks to this, protection from dust and moisture is fully guaranteed.

Interesting! The asynchronous generator is immune to short circuits. Therefore, this energy source is the optimal solution for welding machines. But such devices can be very sensitive to overloads. Therefore, it is prohibited to connect them to devices with initially high inrush currents.

Synchronous

The quality of the current in this case is lower when compared with the previous option. Suitable for providing emergency power in various circumstances:

  • Offices.
  • Refrigeration units.
  • Electrical equipment in dachas and country houses.
  • Construction projects.

Such devices also have some positive qualities:

  • Resistance to short-term overloads.
  • Ability to normally withstand peak loads, including mechanical loads.

But protection from moisture, dust and dirt is worse than that of asynchronous structures. After all, in order to cool, such generators need to pass a certain amount of air through themselves. A synchronous generator will be needed if devices operating with reactive loads are used. Then the power will be less.


Changeover switches

Phasing

It has already been mentioned above. It is worth buying three-phase generators only if there is a consumer with the appropriate characteristics in the house. If all the devices are single-phase, then the generator is selected of this type. This even applies to situations where there is a three-phase network connected to the house.


Network connection

How to connect the generator?

The electric generator can be connected in two ways:

  1. Through a switch (connection to the panel);
  2. Using automatic or semi-automatic reserve input.

The generator is connected to the panel using a changeover or reversing switch:

  1. Before installing it, a cable is laid, depending on the power of the generator.
  2. Then the switch itself is installed in the panel in a special box, protecting it from rust and corrosion.
  3. After that, all that remains is to connect the switch (the main network cable is located on top, the private circuit of the house is in the center, and grounding is below), and start the generator.

Connecting a generator with a semi-automatic automatic transfer switch involves installing two semiconductors in protective boxes that are connected to each other. When the lights go out, you need to start the backup power source, then there will be an automatic transition from the main network to the generator.

Automatic reserve input means turning on the generator automatically, without any intervention.

Connection options

Before moving on to considering specific systems, it is worth understanding why it is necessary to make a special input system. The fact is that many users simply connect the generator through a connector - they say, anyway, the electricity disappears every few months, and there is no point in spending time and money on arranging a connection point.

But connecting through an outlet is fraught with many problems:

  • Lack of a separate machine in the line . This is fraught with problems during interruptions - there is no unit responsible for safety and emergency shutdown in case of emergency situations;
  • Connection point overload . The entire main load falls on one outlet, which often overheats and may even melt and cause a fire;
  • Human factor . Very often it happens that when starting the generator, they forget to turn off the input machine, which causes an overload of the system and the activation of the unit’s protection unit;
  • Possibility of equipment damage . When current is supplied through a city highway and it reaches the contacts of a running electric generator, there is a high probability of equipment failure. Costly repairs or even replacement of the installation may be required.
  • Connecting via an outlet can only be considered as a temporary option

    Option 1 - connection via changeover switches

    In this case, the following generator connection diagram will be used:

    A very simple and understandable design that you can do yourself

    The main element that will be responsible for a safe connection is the changeover switch; its design has the following features:

    The changeover switch has three positions

    • Simplicity . The switch has three modes: 1-0-2. In the first position, the system is powered from a stationary network, in zero all contacts are opened, and in position “2” energy will be supplied from the generator;
    • Easy to connect . Below is a simple instruction, following which anyone can do the work with their own hands, even if they have never worked with electrical networks. The work does not require electrician skills or special equipment;
    • Low cost . A reversible switch (as it is also called) will cost you about 500 rubles, the price is more than affordable.

    Let's figure out how to connect the generator to the house:

    If the walls do not hold sounds well, then you need to additionally soundproof them using special mineral wool or polystyrene foam.

    Below, the entrance to the house is arranged using jumper wires.

    The system startup process is carried out in the following sequence:

    • The machine at the main line input ;
    • The reversing switch switches to power from the generator;
    • Automatic load switches off;
    • The generator starts . For full operation, the equipment warms up for 3-4 minutes;
    • Power is supplied to the changeover switch;
    • Automatic load switches on.

    What types of generators are there?

    Many people think that generators and uninterruptible power supplies are mutually interchangeable and identical. But that's not true. UPS are devices that provide current only for a while. Their work is just enough to save important information on the computer, for example. The generator can produce electricity many times longer.

    There is another device that many also confuse with generators. These are voltage stabilizers. They equalize the voltage if surges occur in the network. Stabilizers protect equipment from sudden changes in network voltage, thereby extending the service life of electrical appliances.

    Before answering the question of how to connect a generator to the home network, you need to understand which generators can be connected to the home network.

    There are three main types of generators based on engine type:

    • gasoline;
    • diesel;
    • gas.

    A gasoline generator is used only for a short time; its operation is not suitable for long-term loads. If the main power source is, then gasoline units should be purchased only to maintain the operation of the devices for a short time (up to 12 hours), if there are frequent network outages.

    The diesel generator is the most powerful unit. This is, in fact, a diesel station that can continuously generate electricity, or be used as a backup generator for lighting the house.

    Gas generators consume the least amount of fuel, which is why they are considered the most economical generators. They can operate either from a gas cylinder or from a gas main.

    Also, both gas and gasoline can be used as fuel in one generator - with the ability to switch. They are called dual-fuel.

    There are two more types of generators - inverter and welding. Both gas and gasoline can be used as fuel.

    Inverter generators have a distinctive feature - performance adjustment. For example, during a power outage, all appliances in the house are connected to the generator. If you turn off any device, automatic performance adjustment will work, and the generator itself will reduce the load.

    Welding generators are designed to power welding machines, mainly manual ones.

    The number of phases and the cooling system also depend on the type of generator.

    Based on the number of phases, generators are divided into single-phase (output voltage 220 V) and three-phase (380 V). The first are used in residential buildings where there is only one power and ground line. A three-phase generator provides power via three power lines, with one grounding line.

    Generators use air or liquid cooling. The first is used on generators or power plants whose power does not exceed 6 kW. Liquid cooling is installed on more powerful generators, the number of engine hours of which is about thirty thousand. It is better to buy such generators on official websites or in specialized stores to prevent interference with the device by unscrupulous sellers.

    How to connect a three-phase generator?

    In the case of using a switch, a winding is required for each phase separately, that is, a jumper from one phase to another.

    How can I not connect?

    If the generator is not properly connected to the home network, a fire may occur. To prevent this from happening:

    • Do not use two machines, one of which is from a gas generator, and the other from the central network. There is a big risk of powering the house from two sources at once;
    • You cannot power devices from a gas generator using the “socket-socket” method. If the load is higher than the outlet can withstand, it will fail, like all the wiring in the house.

    A gasoline generator solves problems with the supply of electricity. With its help, you will not experience interruptions in the supply of electricity, or you will have the opportunity to enjoy the benefits of civilization far from it. However, connecting it to the house is something that not everyone can do. Are you confident that you can connect the unit safely? If not, order the services of professionals. Life costs more.

    Automatic generator start via AVR unit

    The purpose of such devices is to partially or completely eliminate human participation in the operation of the generator. There are two main types of such devices. The first completely copies the auto-switching system, which operates on two starters, but with the addition of an electronic unit for starting and stopping the generator. A low-current cable is connected to it from the main power supply line, through which the unit receives information about the presence or absence of voltage in the network. Depending on this, it sends a command to the engine to start or stop, and switching between input from the main line or from the generator is performed by the starters themselves. In general, this is the same system as the proposed scheme for self-assembly, but here you don’t have to invent anything - just install a ready-made unit.

    The disadvantage of such a block is the same - its purpose is only to start and stop the engine without additional protection.

    The diagram itself looks like this:

    1. Introductory machine. 2. Electricity meter. 3. Automatic generator start block. 4. Generator. 5. Time relay. 6. RCD. 7. Main input contactor. 8. Backup input contactor.

    A more advanced option is a complex system controlled by microprocessor electronics. In general, it works in the same way as a homemade autostart system, but its main advantage is the presence of numerous sensors that monitor all aspects of the generator's operation. If any equipment malfunction occurs, the ATS unit will be able to react adequately - not torment the generator with autostart attempts, but if there is a GSM module, send a message to the owner about the malfunction.

    The ATS unit itself is mounted instead of a distribution panel - this does not require much knowledge - you just need to connect wires from the main line, power and control cables from the generator and output to the house to it.


    1. Introductory machine. 2. Electricity meter. 3. AVR. 4.Generator. 5. Control cable. 6. Consumer machines. 7. Zero bus. 8. Grounding bus.

    Such a unit is a complex set of equipment and its cost in some cases can be equal to the price of a generator. Therefore, its purchase is justified only in case of frequent power outages and for sufficiently powerful generators.

    Types of generators

    Based on the type of fuel used in the unit, all known generating devices can be:

    • gasoline;
    • diesel;
    • units running on gas or wood.

    The first two options attract the attention of users who have taken as a basis a ready-made engine running on gasoline or diesel fuel. According to their purpose, known samples of three-phase current generators are divided into main and backup units

    The question of how to connect to a household network concerns both models

    According to their purpose, known samples of three-phase current generators are divided into main and backup units. The question of how to connect to a household network concerns both models.

    Grounding

    The very principle of operation of the generator involves the periodic occurrence of static electricity on its body, therefore all permanently installed devices necessarily require a separate grounding circuit.

    The ideal option is to create a full-fledged grounding loop, but in general you can get by with the simplest method, for which you will need a metal rod 1.5-2 meters long, a steel bolt or clamp connection and a soft copper wire. A bolt is welded to the iron rod, and the pin itself is driven the entire length into the ground. The copper wire is screwed with one side to the bolt (or clamped with a clamp), and the other to the generator housing - the grounding is ready.

    These are all the main ways to connect a gas generator to the network at home and possible nuances. The presented diagrams will help determine whether it is worth installing autostart systems or whether it will be easier to do with manual switching. Of course, when installing each individual generator, ATS unit or homemade autostart system, additional questions may arise, but they will have to be resolved in each case separately, depending on the device model and the home electrical circuit diagram.

    Connection diagrams

    How to properly connect a gas generator through a switch or three-way switch?
    There are three wires coming from them. The generator network is connected to one, the utility network is connected to the other, and electrical equipment is connected to the third. Power from the mains is connected to the switch at the top, and a wire from the gas generator at the bottom. Electricity consumers are connected to the middle contacts. The switch is installed after the meter, but before the input machines. You can use a semi-automatic connection scheme. After turning off the central power supply, you need to start the device. An additionally installed time relay turns on the gas generator contactor after the engine warms up.

    When the main power supply appears, it will switch to it, and an additional relay will stop the generator.

    Automatic connection is even easier . The AVR system autonomously starts a backup energy source when the city network is turned off. The block is connected to the distribution panel. The connection to the gas generator is made by cable.

    In addition to the use of automatic transfer switches, it is possible to use the following devices: voltage stabilizer, inverter, UPS.

    UPD: Connecting the boiler to the generator.

    Often a generator is purchased to be used in winter to power the heating system boiler. There are some peculiarities here.

    For imported phase-dependent boilers, it is important that the power system has a solidly grounded neutral, i.e. neutral and ground are connected together, and when connecting, the polarity is observed (phase-zero)

    In the case of a portable generator, which is discussed in the article, there is neither zero nor phase. They must be made artificially - one output of the generator will be a phase (L2), and the second (N2) will be placed on the ground, i.e. ground.

    In addition, as is known, boilers are very sensitive to the voltage form. And at the output of a conventional generator, the sine wave is “dirty”; if necessary, I will take an oscillogram. First of all, this happens because... The alternator that generates electricity is brushed, and because of the brushes sparking, failures, and similar unpleasant things occur.

    It is because of this that Off-line and Smart UPS are not suitable for boilers. There at the output there is a quasi-sine with a bunch of harmonics, the oscillograms can be viewed here. And for boilers, Online UPS (double conversion uninterruptible power supplies) is used. For such a UPS, the shape, magnitude and frequency of the input voltage are not particularly important, because it cooks a constant voltage from all this mess, from which it then electronically receives a pure sine wave. And if the boiler is powered through such a UPS, then you can use a regular generator for its backup power.

    For boilers and other sensitive equipment, it is recommended to use inverter generators - this is a generator plus an online UPS. The inverter generator includes a regular generator, which is controlled by a controller, and an inverter, which produces pure sine wave - what boilers need.

    Distribution board diagram with a “network-generator” switch

    Details Published: 04 June 2015

    In dacha areas, garden plots, the private sector and similar places, frequent power outages are common. Here they can turn off the lights for an hour, for the whole day or for a longer time. This creates quite a few problems, since people can no longer imagine life without electricity. He has things working at home: a refrigerator, a TV, room lighting, a pump for watering the garden, and the like.

    Gasoline power plants are very popular in such places. Turn off the lights, start the gas generator and continue to enjoy life. The power plant must be connected to the distribution board through a special outlet. Below I look at the diagram of a distribution board with a “mains-generator” switch, which allows you to switch to power supply from a gas generator when the external network is lost and back.

    Here I am considering manual switching, which is carried out using a reversing switch. All diagrams show an ABB OT40F3C switch. This is a high-quality and reliable reversible switch. It has three positions:

    • the handle is turned to the left - the contacts on its left side are closed, and on the right side they are open;
    • the handle is in a vertical position - all contacts are open (both right and left);
    • the handle is turned to the right - the contacts on its right side are closed, and on the left side they are open.

    If what is written is not entirely clear, then look at the latest diagram and you will immediately understand how it works.

    It is worth noting that if you take such a reversing switch for a higher current, then the switch handle is not included in the kit. It must be purchased separately.

    Below is a simple single-phase switchboard diagram with a mains-generator switch. This is plenty for a small dacha or garden house. If you have a large house, then you need to revise the ratings of the input machine and increase the number of group lines. Everything is individual here.

    It is very convenient to use a network indicator in such panels. For example, the signal lamp LS-47. Why is she needed here? Let's say the lights are turned off and you start the power plant. Everything is working.

    Next, how to determine whether there is voltage in the network or not? You won’t run to the switchboard every half hour and use an indicator to check whether the light is on or not. This is not convenient and is forgotten over time. So you can miss this moment and “sit” on the gas generator until the evening. And gasoline is expensive these days.

    In such a situation, the mains voltage indicator will immediately show you when the light comes on

    It will just light up and you will immediately notice it. It is clearly visible from afar even through the transparent cover of the shield. As soon as the warning light came on, they immediately turned off the power plant and switched the switch to mains mode

    As soon as the warning light came on, they immediately turned off the power plant and switched the switch to mains mode.

    Below is the same diagram of the distribution board, but with an LS-47 signal lamp.

    If you want to protect yourself and your dacha from current leaks, then you need to install an RCD. Below is a diagram with one common protective device. If you want more, then go ahead and fight. Here you can fantasize endlessly.

    For a better understanding of the operation of such a circuit, I schematically showed the state of the contacts of the reversing switch with red lines and the direction of the current with red arrows.

    Below is the work from an external network.

    And here the work from a gas generator is already presented.

    And these are already two diagrams of the operation of this switchboard in one. It looks like a cartoon. Like?

    At the request of site visitors, I am posting below a 3-phase electrical panel diagram with a “network-generator” switch

    Also don't forget to smile:

    A drunk man goes home and hits his head on every lamppost. Then an acquaintance meets him and asks: “Why are you hitting the pillars like that, why are they bothering you?” Can't get around? “That’s not the point at all, it’s just how I determine the way home.” - Didn't understand. - What’s incomprehensible here? Here are 3 more pillars along this street, then 7 more along another - and I’m home.

    How to choose the right three-phase generator


    Three-phase diesel generator PACIFIC I T16K, SDMO (France) 11.6 kW
    When choosing branded units, you will have to take into account the following characteristics:

    • type of energy carrier;
    • device output power;
    • availability of additional functions.

    The type of fuel is selected taking into account specific operating conditions (convenience of storing fuel in a residential building). The output power of the purchased unit is selected taking into account the expected load; this figure varies from 5 to 6 kW for each single-phase branch. When getting acquainted with additional functionality, special attention is paid to the following features:

    • adjustment of 3-phase voltage parameters (its shape, in particular);
    • possibility of connecting additional lines (load capacity);
    • the presence of an electromagnetic relay-regulator.

    It is important to make sure that the selected model has indicator devices that allow you to visually monitor the level of each voltage.

    Connection diagram of a single-phase generator to a three-phase network

    Let's consider the key points of connecting a single-phase generator to a three-phase network. Recently, this topic was created on the forum, and I decided to give a more detailed answer, as well as discuss this issue on the blog, since many readers do not visit the forum.

    Connecting a single-phase generator is relevant for private houses and cottages that want to have an independent power source.

    Many luxury houses (cottages) have three-phase input due to high power consumption. Here the question may arise: what kind of generator is needed? A three-phase generator of the required power suggests itself.

    Generator for a private home

    Is a three-phase generator really necessary?

    I will not give a definitive answer to this answer, however, I assume that a single-phase generator will be cheaper than a three-phase one.

    I have already told you why three-phase input is bad. The main problem is that it is very difficult to achieve uniform phase distribution. Perhaps the generator does not tolerate operating modes very well when there is constant phase imbalance.

    But how can we convert our three-phase shield into a single-phase one?

    Everything is very simple. Scheme for automatically connecting a single-phase generator to a three-phase network:

    Connection diagram of a single-phase DG to a three-phase network

    For this we need only 2 contactors, not counting the auxiliary elements.

    In normal mode, consumers are connected to a three-phase network through the KM1 contactor. If the main power is turned off, the generator starts. Starting can be done using the additional contact of the KM1 contactor. Contactor KM1 is turned off, and contactor KM2 is turned on and combines phase 3 into one.

    If you do not need automatic starting of the generator, then instead of this ATS you can use, for example, a cam switch for the appropriate power. The connection diagram is similar to KM2. Here we must use either two manual switches or 1 switch, and turn off the supply network with an input circuit breaker.

    Which solution is preferable? The choice is yours.

    I also advise you to review my old articles:

    I recommend reading:

    “Scheme for connecting a single-phase generator to a three-phase network”

    “At the same time, do not forget that the power of a single-phase generator will be at least 2 times greater than a three-phase one.”

    They didn’t write about the zero cross section.

    I don't understand the question about power.

    The cross section of the zero is not less than the cross section of the phase wire. For example, VVG-3×16.

    Why will the power of a single-phase generator be at least 2 times greater than a three-phase one?

    About zero. Which cable to lay from the automatic transfer switch to the distribution board with a three-phase input with a power of 15 kW. Emergency diesel is acceptable at 15 kW.

    Single-phase diesel respectively.

    You calculate the current, select the machine, and then select the cable cross-section. At 15kVA - VVG-3×16

    But then how will there be power from the network in three-phase mode?

    The supply cable from the three-phase network will be your own, for example SIP4-4×16 or SIP4-4×25.

    from the support to the ATS and from the diesel engine to the ATS everything is already clear. What kind of cable is placed from the AVR to the distribution board? And why is the power of a single-phase generator 2+ times greater than the power of a three-phase generator?

    After AVR, you will have group lines. There should be no intermediate shields.

    When you transfer all electric motors to one phase, the total Kc should decrease, therefore the power of the single-phase generator will be Pantryk:

    There should be no intermediate shields.

    If the ATS is built into a panel with group devices, then yes, there will be devices right away. And if the AVR is a separate design. It includes two cables (one from the diesel engine and one from the support) and one goes to the panel with group devices. So I’m talking about the zero of such a cable. Or for example, I have a two-story mansion and the allocated power is 30 kW, and I set the diesel to the same 15 kW. At the same time, I have a switchboard for the second floor. It is three phase. It comes with a 5x4 cable. And now we apply common-mode voltage to all phases. What happens to zero? In the particular case with one input distribution board, nothing bad will happen because The tire section is quite sufficient

    But in the general case of using a single-phase generator in a three-phase network, it is worth paying attention to the zero cross-section in three-phase cables and groups

    I did not consider all the nuances in detail, and did not become attached to a specific object. We always need to look at what currents we will have and, depending on them, select machines and cable sections.

    If you have a project, we can discuss it in more detail on the forum.

    Rating
    ( 1 rating, average 5 out of 5 )
    Did you like the article? Share with friends:
    For any suggestions regarding the site: [email protected]
    Для любых предложений по сайту: [email protected]