How to correctly calculate the cross-section and prevent cable overheating

The continuous permissible current of a cable is an important performance characteristic that must be taken into account when calculating the conductor cross-section. If an incorrect value is obtained, then during the use of the electrical network the wire will constantly overheat.

A short-term increase in temperature as a result of a short circuit is possible, but an incorrect cross-section threatens to increase the long-term permissible temperature. This will subsequently lead to damage to the insulation and fire.


When installing electrical wiring, you need to determine the required cable cross-section

Basic Concepts

Any metal product consists of a crystal lattice. Electrons and mobile particles pass through it, which is why electricity is transformed into thermal energy. This property is successfully used by manufacturers of heaters and lighting devices. However, in conventional electrical systems, overheating of the cable is unacceptable, since over time it will lead to insulation failure and fire. Therefore, it is important to select the correct cross-section of conductors so that they can withstand the permissible (potential) current loads of the network.

For this, two terms are taken into account:

  • wire section;
  • current density.


Dependence of current density on cross-section
Even if the correct cross-section of the wire is selected, it can still overheat. There are several reasons: weak contact at the joints or oxidation associated with unacceptable twisting of aluminum and copper conductors.

Wire size

To select the cross-section of the current-carrying core (conductor, and not the entire cable with sheath and insulation), they are guided by two parameters:

  • heating within acceptable limits;
  • loss of voltage.

Overheating of the underground cable placed in plastic hose tubes is dangerous. In overhead power lines, attention is paid to voltage loss. For combined segments with two different sections, select the larger one, rounding it up to the standard value. Before calculating the cross-section or searching for suitable tabular values, you should determine what the operating conditions will be.


An incorrect choice of cable cross-section can lead to overheating and fire.
To calculate the potential heating, the long-term permissible temperature must be taken into account. The value directly depends on the possible current strength Ip. After using the formula, you will receive the calculated current Iр, which should differ from Iп and be less than its value (in no case more!). When choosing a section, use the following formula:

  • Iр = Pн/Un,

Where:

  • Pn — rated power, W;
  • Un — rated voltage, V.

This formula can be used to calculate currents in conductors with an already established temperature, provided that the cable is not affected by other cooling or warming factors. The value of the continuous permissible current Ip depends on various parameters: cross-section, material of manufacture, insulating shell and installation method.

To check the voltage drop on an overhead power line, use the following formula:

  • Up = (U - Un) *100/ Un,

Where:

  • U—voltage from the source;
  • Un is the voltage at the place where the voltage receiver is connected.

The maximum permissible voltage deviation is 10%.

Current Density

This physical quantity is a vector quantity. To designate it, use the Latin letter J. The calculation formula is as follows:

  • J = I/S,

Where:

  • I—current strength, A;
  • S—cross-sectional area, sq. mm.


Limit current density for aluminum and copper wires
Current density is the volume of current that passes through a conductor of a given cross-section in a certain period of time. Measured in A/sq. mm.

Choosing thickness

Once you have determined the power, you can select the cable thickness. Below we will provide a table of wire cross-sections by power and current for a classic copper wire, since aluminum wires are no longer used for wiring today.

Cable cross-section, mmFor 220 VFor 380 V
current, Apower, kWtcurrent, Apower, kWt
1,5until 1741610
2,5265,52516
4378,23020
645104025
1068155032
1685187548

Attention:

When choosing, keep in mind that most Russian manufacturers save on material, and a 4 mm2 cable may actually end up being 2.5 mm2. Practice shows that such “savings” can reach 40%, so be sure to either measure the cable diameter yourself or purchase it with a reserve.

Now let's look at an example of calculating the wire cross-section based on power consumption. So, we have an abstract kitchen, the power of the appliances is 6 kW. We multiply this figure 6*0.8=4.8 kW. The apartment uses one phase, 220 volts. The closest value (you can only take it as a plus) is 5.5 kW, that is, a cable 2.5 square meters thick. Just in case, we have a reserve of 0.7 kW, which “smoothes out” the savings for producers.

It should also be borne in mind that if the wire is working at its limit, it will heat up quickly. Due to heating to 60-80 degrees, the maximum current is reduced by 10-20 percent, which leads to overload and short circuit. Therefore, for critical sections of the chain, an increased coefficient should be used, multiplying the value not by 0.8, but by 1.2-1.3.


Correct calculation of cable thickness is the key to its long service life

Most often, copper structures with a thickness of 1.5 squares are used for laying lighting systems, for sockets - 2.5 squares, for powerful consumers - 4 or 6 squares (machines are installed at 16, 25, 35 and 45A, respectively). But this use is only suitable for standard apartments or houses that do not have powerful consumers. If you have an electric boiler, boiler, oven or other appliances that consume more than 4 kW, then you need to calculate the cables for each specific case, and not use general recommendations.

The above table of cable cross-sections for power and current uses limit values, so if you get calculated numbers that overlap with encyclopedic ones, then try to take the cable with a reserve. For example, if our kitchen had a power of 7 kW, then 7 * 0.8 = 5.6 kW, which is greater than the value of 5.5 for a 2.5 square cable. Take a cable of 4 squares with a reserve or divide the kitchen into two zones by connecting two 2.5 mm2 cables.

Why do you need to calculate the cable cross-section?

When purchasing a cable, you may see different symbols. For example, a 3x5 wire contains three current-carrying conductors, each of which has a cross-section of 5 square meters. mm. Knowing this, just look at the table of voltage and power.

Only a correctly calculated cross-section guarantees the absence of areas with overheating of the cable. In this case, the wire must withstand temporary loads when the current value is 2-3 times greater than the rated value. You will receive a current reserve, which is important, since at any moment the load on the network may increase due to new household appliances. The absence of heating will prevent spontaneous combustion and fires at objects. This point needs to be thought through in advance, since in most cases a hidden method of installing electrical wiring is used, and the slightest damage can lead to the need to replace the entire line.


Electrical power of household appliances

Choose by power

The wire cross-section can be selected depending on the maximum current load on the line. Moreover, each household appliance has a different power. The list below shows the capacities of the most common equipment:

  • electric stove - 5 kW;
  • refrigeration unit - 0.8 kW;
  • dishwasher - 2 kW;
  • microwave - 1.5 kW;
  • kitchen hood - 0.5 kW;
  • kettle - 2 kW.

Obviously, the listed electrical appliances are installed in the kitchen. If you add up all the specified numerical values, you can get the total load on the kitchen electrical network. It will be about 12 kW, but the cross-section should be selected with a margin of up to 30%. Ideally, an electrical cable with a cross-section corresponding to a power of 15-16 kW is laid in the kitchen. To connect the equipment you will need at least two sockets.

The table below shows the selection of copper cable by power:


Determination of copper cable cross-section

The voltage of the electrical network is 220 V. Knowing this parameter and the total load, it is enough to use a simple formula to calculate the current consumption:

  • I = P/U = 16,000/220 = 72.7 A.

This is the maximum permissible current for the cable being laid, but in fact the household appliances listed above will consume about 56-57 A. However, it is not necessary to exclude situations when other devices will be connected to the network - a vacuum cleaner, additional lamps, and so on. Many electricians avoid calculations using the coefficient 1.3 (30% margin), and simply add another 5 A to the actual value of the permissible current. If this option was possible before, today it is unlikely. Every year this parameter only increases: more powerful refrigerators, washing machines and vacuum cleaners appear.

The table below shows the selection of aluminum cable by power:


Determination of aluminum cable cross-section

Having completed the calculations of the permissible current, proceed to the selection of material for the current-carrying conductors. Aluminum cable costs less than copper cable, but the cross-sectional area of ​​such conductors should be much higher. The current density for aluminum is 8, copper - 10 A/sq. mm.

Normalized current density for cables, A/mm2

Table 3.35

Cable typeТmax, h/year
more than 1000 to 3000more than 3000 to 5000more than 5000
Cables with paper, rubber and polyvinyl chloride insulation with conductors:
copper

aluminum

2,4
1,3
2,0
1D
1,6
1,0
Cables with rubber and plastic insulation with cores:
copper

aluminum

2,8
1,5
2,5
1,4
2,2
1,3

The economic power of the cable line, calculated based on the normalized current density, is given in Table. 3.36 and 3.37.

Current load on the cable: how to calculate the cross-section

The total amount of current moving through a conductor depends on several characteristics: length, width, resistivity and temperature. An increase in temperature is accompanied by a decrease in current. Any reference information that you find in the PUE tables is usually provided for a room temperature of 18 degrees Celsius.

In addition to the electric current, you need to know the conductor material and voltage. The simplest calculation of cable cross-section based on permissible current is to divide its value by 10. If, when studying the table, you do not find the required value, then look for the nearest, slightly larger value. This option is possible for copper wires, and the permissible current is 40 A or less. In the range of 40-80 A, the permissible current should be divided by 8. For aluminum wires, the value is divided by 6. The reason for this was indicated at the end of the previous section.


Permissible current load on the cable

Rule for choosing wire cross-sectional area for maximum current

You can select the required cross-sectional area of ​​the copper wire based on the maximum current using this simple rule:

The required wire cross-sectional area is equal to the maximum current divided by 10.

This rule is given without reserve, back to back, so the result must be rounded up to the nearest standard size. For example, the current is 32 Amps. You need a wire with a cross section of 32/10 = 3.2 mm2. We choose the closest one (naturally, in the larger direction) - 4 mm2. As you can see, this rule fits well into the tabular data.

Important note. This rule works well for currents up to 40 Amps . If the currents are greater (this is already outside the boundaries of an ordinary apartment or house, such currents are at the input) - you need to choose a wire with an even larger margin - divide not by 10, but by 8 (up to 80 A)

The same rule can be stated for finding the maximum current through a copper wire with a known area:

The maximum current is equal to the cross-sectional area multiplied by 10.

And in conclusion - again about the good old aluminum wire.

Aluminum conducts current less well than copper. This is enough to know, but here are some numbers. For aluminum (the same cross-section as the copper wire) at currents up to 32 A, the maximum current will be only 20% less than for copper. At currents up to 80 A, aluminum conducts current 30% worse.

For aluminum the rule of thumb would be:

The maximum current of an aluminum wire is equal to the cross-sectional area multiplied by 6.

I believe that the knowledge given in this article is quite enough to choose a wire based on the ratios “price/thickness”, “thickness/operating temperature” and “thickness/maximum current and power”.

That’s basically all I wanted to tell you about the cross-sectional area of ​​the wires . If something is not clear or you have something to add, ask and write in the comments. If you are interested in what I will publish next on the SamElectric blog, subscribe to receive new articles.

Calculation of cable cross-section by power and length

The length of the cable determines the voltage loss. One potential unpleasant situation: at the end of the selected wire, the voltage has decreased to a minimum, which is not enough to ensure the functionality of the equipment. In household electrical networks, losses will be small, so they can be neglected. It is enough to use a cable with a margin of 100-150 mm, which is necessary to simplify switching. If the edges of the wire are connected to the electrical panel, then the margin should be higher, since the installation of automatic machines is required.

When placing the cable over longer sections, you need to take into account the voltage drop, which is calculated using the formula given above. Any conductor has a certain electrical resistance, which depends on a number of characteristics:

  1. Wire length, m. The longer the length, the higher the losses.
  2. Cross-sectional area, sq. mm. The higher the parameter, the lower the voltage drop.
  3. Specific resistance of the material (look in reference books).


Maximum cable length for various current loads
To calculate the voltage drop in normal cases, it is enough to multiply the resistance and the permissible current. The actual value may be greater, but not more than 5%. If it does not fit within the specified framework, you will have to use a cable with a larger cross-section.

To calculate the cable cross-section for power and length, proceed as follows:

  1. Calculate the current using the formula I=P/(U*cosph), where P is power, U is voltage, cosph is coefficient. In household electrical networks, this coefficient is equal to 1, so the formula simplifies to I=P/U. In industry, cosph is the ratio of active and apparent power (active and reactive).
  2. In the PUE table, find a suitable cable cross-section depending on the current.
  3. Calculate the conductor resistance using the formula: R=ρ*l/S, where ρ is the resistivity of the material from which the conductors are made, l is the cable length, S is the cross-sectional area. Remember that electric current flows in both directions, so the total resistance is equal to twice the value obtained from the formula above.
  4. For voltage drop, use the formula ΔU=I*R
  5. To get the percentage voltage drop, divide ΔU/U.

Thus, if the final value does not exceed 5%, you can leave the cable with the selected cross-section. Otherwise, it will have to be replaced with a conductor with an increased cross-section.

Continuously permissible currents

This value differs depending on the selected cable and the current-carrying cores used. Any wire has a certain long-term temperature Td, which is indicated in its passport. At this temperature, prolonged operation of the conductor cores is permissible, and any damage is excluded.

To calculate the continuous permissible current, use the formula:

  • Id = √((Td*S*Kt)/R),

Where:

  • Ktp - heat transfer coefficient;
  • R - resistance;
  • S - core section.

In practice, you can use PUE tables.


Continuously permissible currents for copper wires and cables

Load table for cable cross-section

The transmission and distribution of electrical energy is completely impossible without wires and cables. It is with their help that electric current is supplied to consumers. Under these conditions, the current load across the cable cross-section, calculated using formulas or determined using tables, becomes of great importance. In this regard, cable cross-sections are selected in accordance with the load created by all electrical appliances.

Preliminary calculations and selection of cross-section ensure uninterrupted passage of electric current. For these purposes, there are tables with a wide range of mutual relationships between the cross section and power and current. They are used even at the stage of development and design of electrical networks, which makes it possible to subsequently eliminate emergency situations that entail significant costs for the repair and restoration of cables, wires and equipment.

The existing table of cable current loads given in the PUE shows that a gradual increase in the conductor cross-section causes a decrease in current density (A/mm2). In some cases, instead of one cable with a large cross-sectional area, it will be more rational to use several cables with a smaller cross-section. However, this option requires economic calculations, since with a noticeable saving in non-ferrous core metal, the costs of installing additional cable lines increase.

Open and closed wiring

Electrical wiring can be of two types:

  • closed;
  • open.

In most cases, hidden installation is used for apartments. Using a hammer drill or wall chaser, special recesses are created in the wall or ceiling into which the cable is laid. Additionally, it can be placed in corrugated tubes or sleeves. Having hidden the cable, the recesses should be sealed with plaster. The only acceptable option for modern hidden wiring is copper conductors. In this case, you should consider in advance the potential expansion of the network or the process of partial replacement of its components. Ideally, you should use flat wires.


Laying hidden wiring in grooves

Open electrical wiring involves placing the cable along surfaces. Mainly flexible conductors with a round cross-section are used. They are placed in cable ducts or passed through corrugations. When calculating the load, the cable laying method must be taken into account.

Selection of wire cross-section according to the number of consumers

When calculating cross-sections for an electrical cable in an apartment, it is first recommended to show the wiring schematically. The drawing must indicate all devices that consume electricity. The circuit is divided into different rooms, since each can use a wire of a different cross-section.


Wiring diagram for consumers

The electrical network is divided into several circuits. Each circuit corresponds only to those electrical appliances that are connected to it. To select a cable connecting all circuits, you need to calculate the total total power. This is the main criterion for choosing a section. Each subsequent branching (branch) will lead to a decrease in the total power and, accordingly, a decrease in the required cross-section.

Current loads in DC networks

When calculating the current load in a direct current network, they are guided by a single-core cable. The voltage of this current is 12 V. Calculation of the load of the wire through which a 0.1 kW light bulb is connected (for example, in the headlight of a car) looks like this:

  • I = P/U = 100/12 ~ 8.35 A.

After this, it is easy to calculate the resistance:

  • R = U/I = 12/8.35 = 1.44 Ohm.

In the table, find the resistivity of copper, from which the cores of modern conductors are made. Also assume that the cable length is 2 m. Use the formula given in the sections above to obtain the cross-sectional area of ​​the suitable wire:

  • S = (ρ*L)/R = (1.68*10-8*2)/1.44 = 1.2 sq. mm.


Selecting a cable cross-section for DC networks
When studying the PUE, you can find countless tables that define the current load for AC networks with single- and three-phase circuits. Therefore, it is not necessary to perform such complex calculations.

Electrical laboratory » Questions and answers » PUE 7th edition » 1.3.10 - 1.3.11. Permissible continuous currents for wires, cords and cables with rubber or plastic insulation

PERMISSIBLE CONTINUOUS CURRENTS FOR WIRES, CORDS AND CABLES WITH RUBBER OR PLASTIC INSULATION

1.3.10. Permissible long-term currents for wires with rubber or polyvinyl chloride insulation, cords with rubber insulation and cables with rubber or plastic insulation in lead, polyvinyl chloride and rubber sheaths are given in Table. 1.3.4-1.3.11. They are accepted for temperatures: cores +65, ambient air +25 and ground + 15°C. When determining the number of wires laid in one pipe (or cores of a stranded conductor), the neutral working conductor of a four-wire three-phase current system, as well as grounding and neutral protective conductors are not taken into account. The data contained in the table. 1.3.4 and 1.3.5 should be applied regardless of the number of pipes and the location of their installation (in the air, floors, foundations). Permissible long-term currents for wires and cables laid in boxes, as well as in trays in bundles, must be accepted: for wires - according to table. 1.3.4 and 1.3.5 as for wires laid in pipes, for cables - according to table. 1.3.6-1.3.8 as for cables laid in the air. If the number of simultaneously loaded wires is more than four, laid in pipes, boxes, and also in trays in bundles, the currents for the wires should be taken according to the table. 1.3.4 and 1.3.5 as for wires laid openly (in the air), with the introduction of reduction factors of 0.68 for 5 and 6; 0.63 for 7-9 and 0.6 for 10-12 conductors. For secondary circuit wires, reduction factors are not introduced.

Table 1.3.4. Permissible continuous current for wires and cords with rubber and polyvinyl chloride insulation with copper conductors

Section

conductive

cores, mm2

Current, A, for wires laid
open in one pipe
two single-core three single-core four single-core one two-core one three-wire
0,5 11
0,75 15
1 17 16 15 14 15 14
1,2 20 18 16 15 16 14,5
1,5 23 19 17 16 18 15
2 26 24 22 20 23 19
2,5 30 27 25 25 25 21
3 34 32 28 26 28 24
4 41 38 35 30 32 27
5 46 42 39 34 37 31
6 50 46 42 40 40 34
8 62 54 51 46 48 43
10 80 70 60 50 55 50
16 100 85 80 75 80 70
25 140 115 100 90 100 85
35 170 135 125 115 125 100
50 215 185 170 150 160 135
70 270 225 210 185 195 175
95 330 275 255 225 245 215
120 385 315 290 260 295 250
150 440 360 330
185 510
240 605
300 695
400 830

Table 1.3.5. Permissible continuous current for rubber and polyvinyl chloride insulated wires with aluminum conductors

Section

conductive

cores, mm2

Current, A, for wires laid
open in one pipe
two single-core three single-core four single-core one-two-core one three-wire
2 21 19 18 15 17 14
2,5 24 20 19 19 19 16
3 27 24 22 21 22 18
4 32 28 28 23 25 21
5 36 32 30 27 28 24
6 39 36 32 30 31 26
8 46 43 40 37 38 32
10 60 50 47 39 42 38
16 75 60 60 55 60 55
25 105 85 80 70 75 65
35 130 100 95 85 95 75
50 165 140 130 120 125 105
70 210 175 165 140 150 135
95 255 215 200 175 190 165
120 295 245 220 200 230 190
150 340 275 255
185 390
240 465
300 535
400 645

Table 1.3.6. Permissible continuous current for wires with copper conductors with rubber insulation in metal protective sheaths and cables with copper conductors with rubber insulation in lead, polyvinyl chloride, nayrite or rubber sheaths, armored and unarmored

Section

conductive

cores, mm2

Current *, A, for wires and cables
single-core two-wire three-wire
when laying
in the air in the air in the ground in the air in the ground
1,5 23 19 33 19 27
2,5 30 27 44 25 38
4 41 38 55 35 49
6 50 50 70 42 60
10 80 70 105 55 90
16 100 90 135 75 115
25 140 115 175 95 150
35 170 140 210 120 180
50 215 175 265 145 225
70 270 215 320 180 275
95 325 260 385 220 330
120 385 300 445 260 385
150 440 350 505 305 435
185 510 405 570 350 500
240 605

___________ * Currents apply to wires and cables both with and without a neutral core.

Table 1.3.7. Permissible continuous current for cables with aluminum conductors with rubber or plastic insulation in lead, polyvinyl chloride and rubber sheaths, armored and unarmored

Section

conductive

cores, mm2

Current, A, for cables
single-core two-wire three-wire
when laying
in the air in the air in the ground in the air in the ground
2,5 23 21 34 19 29
4 31 29 42 27 38
6 38 38 55 32 46
10 60 55 80 42 70
16 75 70 105 60 90
25 105 90 135 75 115
35 130 105 160 90 140
50 165 135 205 110 175
70 210 165 245 140 210
95 250 200 295 170 255
120 295 230 340 200 295
150 340 270 390 235 335
185 390 310 440 270 385
240 465

Note. Permissible continuous currents for four-core cables with plastic insulation for voltages up to 1 kV can be selected according to table. 1.3.7, as for three-core cables, but with a coefficient of 0.92.

Table 1.3.8. Permissible continuous current for portable light and medium hose cords, portable heavy duty hose cables, mine flexible hose cables, floodlight cables and portable wires with copper conductors

Conductive cross-section

cores, mm2

Current *, A, for cords, wires and cables
single-core two-wire three-wire
0,5 12
0,75 16 14
1,0 18 16
1,5 23 20
2,5 40 33 28
4 50 43 36
6 65 55 45
10 90 75 60
16 120 95 80
25 160 125 105
35 190 150 130
50 235 185 160
70 290 235 200

________________ * Currents refer to cords, wires and cables with and without a neutral core

Table 1.3.9. Permissible continuous current for portable hose cables with copper conductors and rubber insulation for peat enterprises

Conductive cross-section

cores, mm2

Current *, A, for cables with voltage, kV
0,5 3 6
6 44 45 47
10 60 60 65
16 80 80 85
25 100 105 105
35 125 125 130
50 155 155 160
70 190 195

_____________ * Currents refer to cables with and without a neutral core.

Table 1.3.10. Permissible continuous current for hose cables with copper conductors and rubber insulation for mobile electrical receivers

Section

conductive

cores, mm2

Current *, A, for cables with voltage, kV Conductor cross-section, mm2 Current *, A, for cables with voltage, kV
3 6 3 6
16 85 90 70 215 220
25 115 120 95 260 265
35 140 145 120 305 310
50 175 180 150 345 350

__________________ * Currents refer to cables with and without a neutral core.

Table 1.3.11. Permissible continuous current for wires with copper conductors with rubber insulation for electrified transport 1.3 and 4 kV

Conductor cross-section, mm2 Current, A Conductor cross-section, mm2 Current, A Conductor cross-section, mm2 Current, A
1 20 16 115 120 390
1,5 25 25 150 150 445
2,5 40 35 185 185 505
4 50 50 230 240 590
6 65 70 285 300 670
10 90 95 340 350 745

Table 1.3.12. Reduction factor for wires and cables laid in boxes

Way Number of laid

wires and cables

Reduction factor for power supply wires
gaskets single-core stranded separate electrical receivers with a utilization factor of up to 0.7 groups of electrical receivers and individual receivers with a utilization factor of more than 0.7
Multilayer

and bunches

Up to 4 1,0
2 5-6 0,85
3-9 7-9 0,75
10-11 10-11 0,7
12-14 12-14 0,65
15-18 15-18 0,6
Single layer 2-4 2-4 0,67
5 5 0,6

1.3.11. Permissible long-term currents for wires laid in trays, when laid single-row (not in bundles), should be taken as for wires laid in the air. Permissible long-term currents for wires and cables laid in boxes should be taken according to table. 1.3.4-1.3.7 as for single wires and cables laid openly (in the air), using the reduction factors indicated in table. 1.3.12. When choosing reduction factors, control and reserve wires and cables are not taken into account.

Causes of cable heating

Current-carrying conductors can overheat for several reasons, which are directly related to the nature of the electric current. The electric field sets in motion electrons, which move along the selected conductor. In the crystal lattices of which metals are composed, strong molecular bonds operate. Imagine a table tennis ball and a spider web. The second one is more or less durable, the first one is light in weight, so in order for the ball to break the web, more effort will have to be made. The harder you swing, the more tense your muscles will be. The higher the voltage, the higher the energy expended. Accordingly, the muscles will heat up more.

Likewise, electrons are forced to release more heat, spending a lot of energy to overcome these molecular bonds. This process is called the conversion of electrical energy into thermal energy.

This phenomenon can be compared with the release of heat during friction. We can say that electrons are forced to rub against the crystal lattice of the metal and thereby generate heat. This property of a metal cable has its advantages and disadvantages. Heating can be useful in manufacturing facilities and for household appliances. It is the main property that allows electric stoves, heaters, irons and kettles to operate. However, in conventional electrical networks this can lead to overheating and destruction of the insulation, and subsequently even to a fire. Machinery and equipment may deteriorate. A similar thing happens if the specified norm for long-term current loads is exceeded.

We list three main reasons for conductor overheating:

  1. The most common is the use of a cable with an incorrect cross-section. Any conductor has a unique maximum current carrying capacity. It is measured in Amperes. Before connecting a household appliance, you need to determine its power and, in accordance with it, select the correct cross-section. It is important to take into account a margin of 30-40%.
  2. The second reason is the lack of high-quality contact at the connection points of the line. We are talking about sections of the route where the cable is connected to a panel, circuit breaker or switch. Poor contact leads to heating. In worst case scenarios - complete burnout. In most cases, it will be enough to inspect the contacts and tighten all connections.
  3. The old electrical wiring was built on aluminum conductors, so when modernizing such cable lines there is often a need to switch to copper conductors. In this case, it is important to follow the technique for connecting copper and aluminum conductors. Without the use of special terminal blocks, the appearance of oxidation is a matter of time.


Old aluminum wiring in the apartment

Calculation of permissible current for heating cores

If a conductor of a suitable cross-section is selected, this will eliminate voltage drop and overheating of the line. Thus, the cross-section determines how optimal and economical the operating mode of the electrical network will be. It would seem that you can simply take and install a cable with a huge cross-section. But the cost of copper conductors is proportional to their cross-section, and the difference when installing electrical wiring in just one room can amount to several thousand rubles. Therefore, it is important to be able to correctly calculate the cable cross-section: on the one hand, you guarantee the safe operation of the network, on the other hand, you will not spend extra money on purchasing an overly “thick” conductor.

To select the wire cross-section, two important criteria must be taken into account - permissible heating and voltage loss. Having received two values ​​for the cross-sectional area of ​​the conductor using different formulas, choose the larger value, rounding it to the standard. Overhead power lines are especially sensitive to voltage loss. At the same time, for underground lines and cables placed in corrugated pipes, it is important to take into account the permissible heating. Thus, the cross-section should be determined depending on the type of wiring.


Permissible heating temperatures of current-carrying cable cores

Id - permissible load on the cable (heating current). This value corresponds to the current flowing through the conductor over a long period of time. In the process of this, a set, long-term permissible temperature (Td) appears. The calculated current strength (Ip) must correspond to the permissible current (Id), and to determine it you need to use the formula:

  • Iр=(1000*Pн*kз)/√(3*Un*hд*cos j),

Where:

  • Pn — rated power, kW;
  • Kz - load factor (0.85-0.9);
  • Un — rated voltage of the equipment;
  • hd - equipment efficiency;
  • cos j - equipment power factor (0.85-0.92).

It turns out that for any long-term permissible current flowing through the conductor, there corresponds a specific value of the established, long-term permissible heating temperature. It is important to neutralize the influence of other environmental factors. The cable current directly depends on the material from which the insulation is made, the laying method, the cross-section and material of the cores in the conductor.

Even if we take into account the same current values, the thermal output will be different depending on the ambient temperature. The lower the temperature, the more efficient the heat transfer.


Cable correction factors depending on ambient temperature

Temperatures differ depending on the region and time of year, so in the PUE you can find tables for specific values. If the temperature differs significantly from the calculated one, correction factors will have to be used. The base temperature indoors or outdoors is 25 degrees Celsius. If the cable is laid underground, the temperature changes by 15 degrees Celsius. However, it is underground that it remains constant.

Permissible continuous currents for wires, cords and cables with rubber or plastic insulation

Permissible continuous currents for wires with rubber or polyvinyl chloride insulation, cords with rubber insulation and cables with rubber or plastic insulation in lead, polyvinyl chloride and rubber sheaths

  • Permissible continuous current for wires and cords with rubber and polyvinyl chloride insulation with copper conductors
  • Permissible continuous current for rubber and polyvinyl chloride insulated wires with aluminum conductors
  • Permissible continuous current for wires with copper conductors with rubber insulation in metal protective sheaths and cables with copper conductors with rubber insulation in lead, polyvinyl chloride, nayrite or rubber sheaths, armored and unarmored
  • Permissible continuous current for cables with aluminum conductors with rubber or plastic insulation in lead, polyvinyl chloride and rubber sheaths, armored and unarmored
  • Permissible continuous current for portable light and medium hose cords, portable heavy duty hose cables, mine flexible hose cables, floodlight cables and portable wires with copper conductors
  • Permissible continuous current for portable hose cables with copper conductors and rubber insulation for peat enterprises
  • Permissible continuous current for hose cables with copper conductors and rubber insulation for mobile electrical receivers
  • Permissible continuous current for wires with copper conductors with rubber insulation for electrified transport 1, 3 and 4 kV

Permissible continuous current for wires and cords with rubber and polyvinyl chloride insulation with copper conductors

Conductor cross-section, mm2Current, A, for wires laid
open in one pipe
two single core three single core four single core one two core one three core
0,5 11
0,75 15
1 17 16 15 14 15 14
1,2 20 18 16 15 16 14,5
1,5 23 19 17 16 18 15
2 26 24 22 20 23 19
2,5 30 27 25 25 25 21
3 34 32 28 26 28 24
4 41 38 35 30 32 27
5 46 42 39 34 37 31
6 50 46 42 40 40 34
8 62 54 51 46 48 43
10 80 70 60 50 55 50
16 100 85 80 75 80 70
25 140 115 100 90 100 85
35 170 135 125 115 125 100
50 215 185 170 150 160 135
70 270 225 210 185 195 175
95 330 275 255 225 245 215
120 385 315 290 260 295 250
150 440 360 330
185 510
240 605
300 695
400 830

Permissible continuous current for rubber and polyvinyl chloride insulated wires with aluminum conductors

Conductor cross-section, mm2 Current, A, for wires laid
open in one pipe
two single-core three single-core four single-core one two-wire one three-wire
2 21 19 18 15 17 14
2,5 24 20 19 19 19 16
3 27 24 22 21 22 18
4 32 28 28 23 25 21
5 36 32 30 27 28 24
6 39 36 32 30 31 26
8 46 43 40 37 38 32
10 60 50 47 39 42 38
16 75 60 60 55 60 55
25 105 85 80 70 75 65
35 130 100 95 85 95 75
50 165 140 130 120 125 105
70 210 175 165 140 150 135
95 255 215 200 175 190 165
120 295 245 220 200 230 190
150 340 275 255
185 390
240 465
300 535
400 645

Permissible continuous current for wires with copper conductors with rubber insulation in metal protective sheaths and cables with copper conductors with rubber insulation in lead, polyvinyl chloride, nayrite or rubber sheaths, armored and unarmored

Conductor cross-section, mm2 Current, A, for wires and cables
single-core two-wire three-wire
when laying
in the air in the air in the ground in the air in the ground
1,5 23 19 33 19 27
2,5 30 27 44 25 38
4 41 38 55 35 49
6 50 50 70 42 60
10 80 70 105 55 90
16 100 90 135 75 115
25 140 115 175 95 150
35 170 140 210 120 180
50 215 175 265 145 225
70 270 215 320 180 275
95 325 260 385 220 330
120 385 300 445 260 385
150 440 350 505 305 435
185 510 405 570 350 500
240 605

* Currents apply to wires and cables both with and without a neutral core.

Permissible continuous current for cables with aluminum conductors with rubber or plastic insulation in lead, polyvinyl chloride and rubber sheaths, armored and unarmored*

Conductor cross-section, mm2 Current, A, for wires and cables
single-core two-wire three-wire
when laying
in the air in the air in the ground in the air in the ground
2,5 23 21 34 19 29
4 31 29 42 27 38
6 38 38 55 32 46
10 60 55 80 42 70
16 75 70 105 60 90
25 105 90 135 75 115
35 130 105 160 90 140
50 165 135 205 110 175
70 210 165 245 140 210
95 250 200 295 170 255
120 295 230 340 200 295
150 340 270 390 235 335
185 390 310 440 270 385
240 465

*Note. Permissible continuous currents for four-core cables with plastic insulation for voltages up to 1 kV can be selected as for three-core cables, but with a coefficient of 0.92.

Permissible continuous current for portable light and medium hose cords, portable heavy duty hose cables, mine flexible hose cables, floodlight cables and portable wires with copper conductors

Conductor cross-section, mm2 Current, A, for cords, wires and cables
single-core two-wire three-wire
0,5 12
0,75 16 14
1,0 18 16
1,5 23 20
2,5 40 33 28
4 50 43 36
6 65 55 45
10 90 75 60
16 120 95 80
25 160 125 105
35 190 150 130
50 235 185 160
70 290 235 200

* Currents apply to cords, wires and cables with and without a neutral core.

Permissible continuous current for portable hose cables with copper conductors and rubber insulation for peat enterprises

Conductor cross-section, mm2 Current, A, for cables with voltage, kV
0,5 3 6
6 44 45 47
10 60 60 65
16 80 80 85
25 100 105 105
35 125 125 130
50 155 155 160
70 190 195

* Currents refer to cables with and without a neutral core.

Permissible continuous current for hose cables with copper conductors and rubber insulation for mobile electrical receivers

Conductor cross-section, mm2 Current, A, for cables with voltage, kV Conductor cross-section, mm2 Current*, A, for cables with voltage, kV
3 6 3 6
16 85 90 70 215 220
25 115 120 95 260 265
35 140 145 120 305 310
50 175 180 150 345 350

* Currents refer to cables with and without a neutral core.

Permissible continuous current for wires with copper conductors with rubber insulation for electrified transport 1, 3 and 4 kV

Conductor cross-section, mm2 Current, A Conductor cross-section, mm2 Current, A Conductor cross-section, mm2 Current, A
1 20 16 115 120 390
1,5 25 25 150 150 445
2,5 40 35 185 185 505
4 50 50 230 240 590
6 65 70 285 300 670
10 90 95 340 350 745

Heat transfer conditions

An important condition for heat transfer is the humid environment in which the cable is located. When placing a wire in the ground, heat removal is directly related to the structure and its composition, as well as the level of humidity.

To obtain the most accurate values, you will have to analyze the composition of the soil, depending on which the resistance will vary. Using the table, look for resistivity. Thanks to high-quality compaction, this characteristic can be reduced. Sand and gravel have lower thermal conductivity compared to clay, so ideally the wires are buried last. Instead of clay, you can use loam without admixtures of slag, stones and debris.

The heat dissipation of the air cable is minimal. The parameter decreases for lines in cable ducts that have an air gap. Cables located close to each other heat each other, so current loads should be kept as low as possible. Permissible currents are calculated using two different formulas depending on the operating mode - emergency or long-term. If a short circuit occurs, the permissible temperature for a paper-insulated wire is 200, PVC - 120 degrees Celsius.

It is important to remember the different cooling conditions for cables with and without insulation. In the first case, the heat flows emanating from the heating of the cores are forced to overcome an additional barrier in the form of an insulating layer.


Cable location in trench

When laying cables underground, when two conductors are located in one trench at once, the cooling process will slow down significantly, which will lead to a reduction in permissible current loads.

From the point of view of electrical and fire safety, determining the correct long-term permissible current and cable cross-section is an important condition to prevent overheating, insulation failure and ignition of the cable line. When making calculations, you should be careful and take into account many additional conditions. Certain adjustments are needed even for tabular values.

Rating
( 2 ratings, average 4.5 out of 5 )
Did you like the article? Share with friends:
For any suggestions regarding the site: [email protected]
Для любых предложений по сайту: [email protected]