Cable burning technique used installations for burning

In recent years, non-burning methods for searching for damage to energy cables have become quite widespread in Russia. The possibilities for using such methods in the Russian power grid remain limited. This is due to the fact that most of the cable lines remain unrouted, and on such cables, no-burning methods and acoustic search alone will not do. Therefore, the most popular scheme for searching for faults on energy cables in Russia remains and will remain in the coming years the following scheme:

The key to effective work under this scheme is high-quality burning installations from the ANGSTREM company. To find faults using pulse reflectometry and induction search, burning is required to ensure the transformation of high-resistance single-phase cable faults into low-resistance two or three-phase cables with the appearance of a reliable metal bridge at the damage site. If during burning it is possible to achieve a short circuit between the core and the core, then problems with finding the exact location of the damage no longer arise. On the other hand, “pumping” high power into the cable during the burning process should not lead to the cable failing in other places.

Burning a high-voltage cable is a preparatory procedure that ensures the possibility of using a set of weapons of mass destruction methods. Some OMP methods are applicable only when the transient resistance at the site of insulation damage is no more than hundreds or even units of Ohms (in some cases, tenths of an Ohm). Reducing the contact resistance is the task of burning.

Burning process technology:

First stage

— preliminary high-voltage burning of the cable, carried out using high voltage and low currents until a breakdown occurs in the cable. A standard burning installation produces a maximum voltage of about 20–25 kV. The high-voltage burning process occurs as follows: a minimum voltage is applied to the damaged cable and then it gradually rises to 20–25 kV or to the value at which breakdown can be achieved, after which the burning process begins.

The maximum voltage when burning a cable should not exceed 0.5–0.7 U isp., however, in practice, such voltage is not always enough to carry out preliminary burning. If a burning installation that produces a maximum voltage of 20–25 kV is not able to provide cable breakdown, an additional installation with a maximum voltage of 60–70 kV, but with less power, is used in combination with it. Equipment of this type is called installations for testing and burning high-voltage cables; they can be connected to the burning installation or used separately.

Second phase

- burning of the cable begins from the moment of breakdown and the occurrence of a short circuit and is carried out by lowering the voltage and increasing the current until the single-phase circuit is converted into two or three-phase (welding core to core). Initially, the high voltage source destroys the cable insulation with a minimum current, then, as the burn is carried out, the voltage values ​​gradually decrease and the current values ​​increase.

In the case of additional use of a testing and burning installation with a maximum voltage of 60–70 kV, it carries out the burning process with a voltage from 60–70 kV to 20–25 kV, after which the main burning installation, which has a higher power, is automatically switched on.

Third stage

— afterburning of the cable is the final stage of burning and is carried out at low voltages and high currents of the order of 20–60 A, depending on the model of the burning installation. This stage is carried out using a low-voltage source, which is automatically connected when the voltage drops to certain values.

In the event of a short circuit of one core to the shell, to destroy the conductive bridge between the core and the shell, special sufficiently powerful burning installations are used, capable of delivering high current values ​​(300 A). It should be noted that the use of installations of this type can lead to a decrease in the life of the cable and its damage in other, “weak” places.

Diagram of a device for welding two cores in a faulty cable - SamElectric.ru blog

I present to the readers the first article of the summer competition. I remind you that all articles of the previous competition, as well as the rules and results, can be seen at this link.

Author – Marchenko Boris Danilovich.

I am an electrical engineer, retired. From time to time, active power engineers and heads of local enterprises approach me with various requests. I have several publications in specialized journals.

If the rules of technical operation of electrical cables are not followed, especially with paper insulation of type AAB-1 3*35, AAB 3*120, during prolonged operation, a “breakdown” (short circuit) is observed along the path of core - core or core - grounding shell.

The operation service learns that a “breakdown” has occurred after the automatic protection of the cable breaker is triggered. The consumer is left without electricity. You need to find the location of the “breakdown” in the cable and eliminate the fault.

The actual use of the device in practice was repeatedly successfully used by me on underground cables at a depth of up to one meter. In all cases, welding of the cores was successful.

READ MORE: Laying cables in the floor of a house or apartment, PUE technology

To control the fact of welding, a conventional incandescent lamp is used, and localization of the welding site (i.e.

The point where the cable “breaks down” is the core - the core has an insulation resistance in the range of 500...100 kOhm. To more accurately determine the location of the damage, devices such as R5-10, R5-13, etc., a sound generator and a cable finder are used.

But for normal operation of search devices, it is necessary to reduce the cable insulation resistance to 10...2 ohms. To reduce the resistance, it is necessary to “burn out” the cable. For this purpose, devices such as UP-7, “fenik”, etc. are used.

which may or may not be available.

I offer my simple diagram of a device for welding cable cores. Due to the fact that the voltage in the 220 V cable causes a “breakdown” and the protection is triggered, this can be used for welding the core with the protective core of the cable. You only need to limit the current, turn on a resistance and a time relay in series to limit the welding time.

Fig.1. Diagram of a device for welding cores in a faulty cable.

These are: a PME-211 starter with a 220 V coil, an A1 circuit breaker with an operating current of 150 ... 200 A, two powerful resistances R1 = 1.8 ohms and R2 = 1.8 ohms with a power of P = 500 W, which can be turned on if necessary sequentially. Time relay 4...10 sec. powered by a 220/24 transformer, 24 volts DC.

Other parts are an input circuit breaker with an operating current of 150-200 A, a current transformer 200/5, an ammeter 5A, a current relay with an operating current of 20A.

To control welding, a 220 V 75 watt lamp is installed. After turning off the PME-211 starter, if the lamp is on, it means that two cable cores have been welded.

When connecting, be sure to follow the correct connection sequence. One damaged cable core is grounded first. Then Re is connected to terminal X3 of the device. Connect N (zero) to terminal X2. Circuit breaker A1 is turned off and does not supply phase L1 to terminal X1. The device is ready for use.

Several attempts have been made to weld a power cable core to a grounded cable sheath. A positive result was not always obtained.

When burning, you need to remember fire and electrical safety.

The device is assembled in an old computer case. Weight 15 kg.

Photo of a device for welding cores in an electric cable

Now that the location of the breakdown is clearly marked, you can easily find this place and replace the damaged section of the cable.

Author Marchenko Boris Danilovich

Voting for the contest articles will begin on June 1, but in the meantime, ask questions to the author.

Voting for the authors of the summer competition

  • 1. Marchenko Boris Danilovich with articles on welding cores and searching for hidden wiring (49%, 29 Votes)
  • 3. Sergey Pikalov with an article about wiring in construction (34%, 20 Votes)
  • 2. Alexey Sidorkin with an article about repairing a Bosch drill (17%, 10 Votes)

Total failures: 59

Loading …

(35.00 out of 5)Loading…

Types of cable burning units supplied

Name of equipmentTesting and burning installations (60-70 kV)Burning installations (voltage 20 - 25 kV, current from 20 A)Afterburning installations for destroying the bridge between the core and the sheath (current 300 A)
AIP-70
VPU-60 (replaces AID-60P “Vulcan”)
APU-1-3M
APU-2M
MPU-3 "Phoenix"
UD-300
UD-300M
AIP-70 + APU-1-3M
AIP-70 + APU-2M
IPK-1, VPU-60 + MPU-3 “Phoenix”

The ANGSTREM company supplies three types of burning installations:

  1. Installations for testing and burning high-voltage cables with a maximum voltage of 60–70 kV, used as auxiliary equipment in the initial stages of burning.
  2. Burning installations with a maximum voltage of 20–25 kV, with several high-voltage and one low-voltage sources.
  3. Afterburning installations designed to destroy the metal bridge between the core and the sheath with high currents (300 A) in the event of a single-phase short circuit to the core.

When choosing a particular model, it is necessary to take into account both production tasks and the characteristics of existing equipment and its compatibility with the purchased one.

An example of compatibility of ANGSTREM equipment for burning

Great Encyclopedia of Oil and Gas

The cable burning process consists of several stages. The first stage of cable burning begins from the moment of breakdown of the damaged insulation when tested with rectified voltage from a kenotron installation, which produces currents in milliamps at tens of kilovolts.

The kenotron installation is used until the transition resistance at the breakdown site decreases with each subsequent switch on.

To further reduce the transition resistance in the absence of special equipment (gastronic installation), three-phase power transformers of the TM-6 / 0 4 type with a power of 30 - 50 kVA are used for burning the cable.  

Acoustic method (see Fig. 11.

7 6) are used to determine directly on the route the location of all types of damage to the cable line, provided that a sound boom is created in this place, perceived on the surface of the earth using an acoustic apparatus.

To create an electrical discharge, there must be a through hole at the site of cable damage, formed by burning the cable with a gastronic installation, as well as sufficient transition resistance for the formation of a spark discharge.  

The presence of higher harmonics in the network voltage leads to an increased content of them in the ground fault current, which reduces the efficiency of arc extinguishing devices. Due to higher harmonics of the current, quite often single-phase short circuits turn into two-phase ones at the site of the first breakdown due to cable burning.  

External view of the kenotron apparatus.  

When used to work directly on the network, it is installed on a car, and installation and removal is inconvenient due to the significant weight of the device.

Therefore, in power systems with a developed cable network, it is advisable to have special testing vehicles; collecting in them the equipment necessary for testing and burning cables. Such vehicles are sometimes called mobile laboratories. The car body, in addition to the driver's cab, has two compartments.

The compartment located at the rear of the driver's cab houses the control panel and the operator's seat. The rear compartment houses test and measurement equipment.  

Important

The time for testing cables with increased voltage is set to 10 minutes. The time is counted from the moment the test voltage is brought to the specified value.

If, during testing, an increase in the leakage current is observed depending on the time of application of voltage or leakage current shocks are noticed, then the test time should be increased to 15 - 20 minutes.

In the event of a further increase in the leakage current, the test is carried out until breakdown and burning of the cable.  

The cable burning process consists of several stages. The first stage of cable burning begins from the moment of breakdown of the damaged insulation when tested with rectified voltage from a kenotron installation, which produces currents in milliamps at tens of kilovolts.

The kenotron installation is used until the transition resistance at the breakdown site decreases with each subsequent switch on.

To further reduce the transition resistance in the absence of special equipment (gastronic installation), three-phase power transformers of the TM-6 / 0 4 type with a power of 30 - 50 kVA are used to burn the cable.  

After a breakdown of a cable line due to a failure or as a result of testing, with the exception of direct mechanical damage, there is a need to determine the location of the line damage.

Currently, there are advanced methods by which the location of damage, as a rule, is established with sufficient accuracy and in a limited time.

Advice

Each method has its own area of ​​use, which is determined by the nature of the damage to the cable line and, among other things, the transient resistance that occurs at the site of damage.

In this regard, before determining the location of the damage, it is necessary to determine the nature of the damage, and also, if necessary, burn the cable in order to reduce the transition resistance at the site of damage to its insulation to the required level.

Damage to cable lines is of a different nature: damage to insulation with a short circuit of one core to ground; damage to insulation with short circuit of two or three wires to ground, two or three wires to each other in one or in different places; break of one, two or three cores with grounding and without grounding; floating insulation breakdown; complex injuries containing the specified types of damage. The most common case is damage between the core and the cable sheath, i.e. single-phase damage, especially for cables with conductors in separate sheaths.  

Pages: 1 2 3

Main technical characteristics of burning installations

Name of equipmentMaximum output voltage, kVMaximum output current, ANumber of stepsCharacteristics of stages, kV
APU 1-3M2440425; 5; 1; 0,3
APU-2M3080830; 17; 8; 5; 1,7; 1; 0,3; 0,18
MPU-3 "Phoenix"2020420; 5; 0,6; 0,3
UD-3000,2530010,25
IPK - 1 (VPU - 60 + MPU - 3 Phoenix)6020560; 20; 5; 0,6; 0,3

Operating time without overheating

On complex and inconvenient damage, burning can last several hours.
If the device overheats, the process must be interrupted, which can lead to re-sinking of the damaged area. The longer the continuous operating time of the installation, the better (Table 6). Table 6. Continuous operation time of burning installations from different manufacturers

Name of equipmentContinuous operation time declared by the manufacturer
APU 1-3M5 minutes in burning mode with a floating breakdown, restart after 30 minutes
VUPK-03-25Cyclic work: 1.5 minutes of work - 40 seconds break
MPU-3 PhoenixAbout 3 hours at a temperature of +20°C, without burning time restrictions at temperatures below 0°C
SVP-05TSThe longest continuous operation time at load current: 100% of the maximum - 10 minutes, restart after 5 minutes 70% of the maximum - 30 minutes, restart after 15 minutes
UP-7-3MNo more than 20 minutes, restart after 20 minutes

Important parameters of burning installations

The burning installation consists of several high-voltage sources and one low-voltage one. The maximum current and voltage values ​​of each source are called stages, their number can vary from four to six. During the cable burning process, as the breakdown voltage decreases, the transition to the next burning stage is carried out. As soon as the installation parameters make it possible to switch on a more powerful stage for parallel operation (or separately), it is put into operation. A more powerful stage means a unit with lower internal resistance and higher current.

Main indicators

All of the above indicates that the main characteristics of the device will be the operating current and output voltage. The number of steps is also equally important.

The desired result can be achieved under this condition - the indicators of transient and internal voltage in the damage zone should correspond to each other as closely as possible. In reality, if these parameters differ significantly, the operation of the device is simply impossible.

Only the use of a multi-stage technique will help solve such a problem. The essence of the process is to switch at a lower transient voltage to a source with lower voltage parameters. Stages 3-6 have modern models of burning devices.

Possibility of continuous burning

Old-style burning installations used manual switching of stages by the operator, which often led to interruption of the arc, increased the burning time and created the possibility of “swimming” breakdowns. Modern burning devices are equipped with automatic systems for switching burning stages, eliminating arc rupture at the burning site, which significantly reduces the time spent on preparatory work to find damage sites. Often such burning is called “stepless”, which should not mislead specialists: this concept does not mean the absence of several power units (stages) - simply switching between them is carried out automatically, without operator participation. To generate high voltage, the design of burning installations uses either oil transformers or “dry” transformers. The issue of automatic switching of stages without arc rupture has been resolved in both types of devices, however, there is an opinion that only dry transformers can provide continuous burning in any conditions. This phenomenon is associated with different energy consumption of two types of transformers in short circuit mode. Oil transformers have significantly higher power consumption in short circuit mode, so keeping them turned on simultaneously during the entire burning process is ineffective; therefore, when the voltage drops, the source with the oil transformer, which generates a higher voltage, is turned off. Very often, switching to a more powerful burning stage first leads to “swimming,” i.e. to increase the breakdown voltage, in this case you should return to the previous stage of a higher voltage, and then, after reducing the breakdown voltage, move on to the next stage.

Execution order

Typically, in practice, either a short circuit or a break in the cable cores occurs. The first fault can be high or low resistance. Carrying out a callback shows the presence of a short circuit in the latter case, but for the first option a burning procedure will also be required. This is the only way to penetrate the insulating layer and transform the short circuit into a low-resistance one or transfer a single-phase fault to a 2-3 phase one.

At the first stage, the procedure is performed at low current levels and a sufficiently high voltage. An insulation breakdown and a methodical decrease in voltage are observed in parallel with a decrease in resistance in the defect area. But the current flow rates begin to increase. The resistance decreases by an order of magnitude from kOhm to several ohms.

Dialing methods

There are several ways to ring wires at home:

Using a light bulb and battery

. This is the simplest and fastest method. In order to construct such a device, you need to have a light bulb and a battery (several batteries can be connected together), as well as connecting conductors and a probe. In addition, do not forget that the voltage of the light bulb and the battery should be the same, or the battery should have more, but not vice versa. The connecting wire must be long enough to ring the wire from a distance.


In order for the dialer to work correctly, it is necessary to mark the cable in any order. The operating method of such a device is as follows: a wire that comes from the battery is connected to one core, and a light bulb is attached to the probe. Use this probe to touch the conductors at the opposite end of the cable one by one. If the light comes on, it means this wire is connected to the battery.

You can learn how to ring the wires of a light bulb and a battery from this video lesson:

Using a multimeter

. This device measures various parameters of the electrical network (for example, voltage, current, resistance). In the house, such a device will be indispensable if you need to check an outlet or switch, check for a break, or find out where the wire goes.

You can test the cable with a multimeter using the following method:

  1. The dialing function is installed. Depending on which model of device is used, this mode is designated differently. As a rule, it is indicated by a diode.
  2. Then you need to find the phase in the distribution box. This is done as follows: you need to turn on the power and use an indicator screwdriver to check each cable. We mark the one we need with tape or tape and then determine zero.
  3. After this, you should find the voltage. To do this, set the multimeter to the “voltage measurement” mode. Using a probe, we check each wire. If the next time you touch the probe, it lights up around 220 V, then the right one has been found.

To check the electrical wiring in the wall for integrity, you need to disconnect the cable from the power source. Set the multimeter to resistance measurement mode. When the probes are closed, zeros should appear on the screen.

The video below clearly demonstrates the technology of testing a cable with a multimeter:

These two methods are convenient if the dialing is carried out over a short distance and can be done by one person. If the cable is long and its ends are in different rooms in the apartment or outside, then use a different method.

Using handsets

. Dialing with telephone headsets is carried out as follows: the capsules in the handset are connected to each other and a battery is connected to them, the voltage of which does not exceed two volts. Thanks to this technique, workers can talk to each other over the phone and coordinate their actions.

Cable wiring diagram using telephone handsets:

You can ring as follows: the cable on one side is connected to the tube conductor, and the other conductor is connected to any core. On the other hand, the cable connects to the tube conductor, and the other to each core in turn. If workers can hear each other on the handset, it means they are connected to the same conductor.

You can see the entire technology of work in this video example:

Using a transformer.

There is another way in which you can ring cable lines - this is ringing using a transformer, which has several taps coming from the secondary winding. The technique is as follows: the beginning of the winding is connected to the grounded shell of the conductor, and the transformer taps are connected to the cores and power each of them. If you measure the voltage that exists between the shell at the other end and the conductors, you can determine whether the end belongs to a specific conductor. The dialer will allow you to identify and mark the necessary cores. You can learn how to correctly mark wires from our article.

Rating
( 2 ratings, average 4.5 out of 5 )
Did you like the article? Share with friends:
For any suggestions regarding the site: [email protected]
Для любых предложений по сайту: [email protected]